3. INSTALLATION AND  CONNECTION 

 

3.5  Swimming Pool Heat Pumps Electrical 

iring

 

NOTE: Although the unit heat exchanger is electrically isolated from the rest of the unit, it 
simply prevents the flow of electricity to or from the pool water. Grounding the unit is still 
required to protect you against short circuits inside the unit. Bonding is also required.

 

The unit has a separate molded-in junction box with a standard electrical conduit nipple 
already in place. Just remove the screws and the front panel, feed your supply lines in

 

through the conduit nipple and wire-nut the electric supply wires to the three connections

 

already in the junction box (four connections if three phase). To complete electrical hookup, connect 
Heat Pump by electrical conduit, UF cable or other suitable means as specified (as permitted by 
local electrical authorities) to a dedicated AC power supply branch circuit

 

equipped with the proper circuit breaker, disconnect or time delay fuse protection.

 

 

Disconnect - A disconnect means (circuit breaker , fused or un-fused switch) should be located 
within sight of and readily accessible from the unit, This is common practice on commercial and 
residential air conditioners and heat pumps. It prevents remotely-energizing unattended equipment 
and permits turning off power at the unit while the unit is being

 

serviced.

 

 

3.6  Initial startup of the Unit

 

NOTE- In order for the unit to heat the pool or spa, the filter pump must be running to 
circulate water through the heat exchanger.

 

 

Start up Procedure - After installation is completed, you should follow these steps:

 

1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.

 

2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire 
controller, It should start in several seconds.

 

3. After running a few minutes make sure the air leaving the top(side) of the unit is 
cooler(Between 5-10 

)

 

4. 

ith the unit operating turn the filter pump off. The unit should also turn off automatically,

 

5. Allow the unit and pool pump to run 24 hours per day until desired pool water emperature is 
reached. 

hen the water-in temperature reach setting, The unit just shuts off. The unit will 

now automatically restart (as long as your pool pump is running)when the pool temperature 
drops more than 2

below set temperature.

 

 

Time Delay- The unit is equipped with a 3 minute built-in solid state restart delay included to protect 
control circuit components and to eliminate restart cycling and contactor chatter.

 

This time delay will automatically restart the unit approximately 3 minutes after each control circuit 
interruption. Even a brief power interruption will activate the solid state 3 minute restart delay and 
prevent the unit from starting until the 5 minute countdown is completed. Power interruptions during 
the delay period will have no effect on the 3 minute countdown.

 

 
 
 
 
 
 

 

7

 

Содержание Astral Pool IHPt127

Страница 1: ...ldren or infrm persons without supervision Please ensure that 3 08 2017 INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS Top Discharge Inverter Heat Pumps TOP DISCHARGE INVERTERHEATPUMPS Installation Instruction manual ...

Страница 2: ......

Страница 3: ...l Heat Pumps Location 5 3 3 How Close to Your Pool 5 3 4 Swimming Pool Heat Pumps Plumbing 6 3 5 Swimming Pool Heat Pumps Electrical Wiring 7 3 6 Initial Start up of the Unit 7 4 Usage and Operation 8 4 1 Color screen wire controller interface introduction 8 4 2 Color screen wire controller function introduction 9 4 3 Parameter list and breakdown table 16 4 4 Interface drawin 18 5 Maintenance and ...

Страница 4: ...ccording to the recommended time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has follo...

Страница 5: ...acity Air 10 Water 26 Humid 64 Heating Capacity kW 1 9 8 0 2 6 10 8 4 3 18 2 Heating Capacity Btu 6460 27200 8840 36720 14552 61880 Consumed power kW 0 33 1 95 0 45 2 64 0 74 4 35 COP 4 10 5 76 4 1 5 78 4 18 5 78 Power Supply 230V 1P 50Hz 230V 1P 50Hz 230V 1P 50Hz Casing type ABS Fan Quantity 1 Fan Power Input W 200 200 200 Fan Speed RPM 500 700 500 700 600 800 Sound Pressure 1m dB A 42 54 42 56 4...

Страница 6: ...200 120 IHPt127 IHPt168 IHPt246 Dimensions L W H mm 723 835 865 723 835 865 770 990 970 2 50 87 ...

Страница 7: ...he inlet and outlet are clearly marked Water connections supplied are for 50mm PVC glue in plumbing All automatic sanitising devices must be installed after the heater and in such a way that the sanitiser cannot enter the heater without first mixing with the water in the pool or spa Sanitisers that are connected prior to the heater will void heaterwarranty The Astral Pool Heat Pump Pool Heater is ...

Страница 8: ......

Страница 9: ...40mm ...

Страница 10: ...3 6 Initial startup of the Unit NOTE In order for the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is completed you should follow these steps 1 Turn on your filter pump Check for water leaks and verify flow to and from the pool 2 Turn on the electrical power supply to the unit then press the key ON ...

Страница 11: ...button Parameter Click this button to view the unit state and the parameter CLOCK Press to set the clock the timer on or timer off Fault display Click to view fault history Silent setting Click to turn on off silent function and to set timingLow speed function MODE Click to enter the mode switch interface Water Inlet Temp Click to enter mode setting and the target temp Setting interface 9 Temp cur...

Страница 12: ...ting 2 2 1 Mode switch In the main interface click mode button or inlet water temperature setting button interface displays as follows Click the refrigeration mode button automatic mode button or heating mode button then you can select the corresponding mode Note when the unit is designed for single automatic mode or single thermal mode the mode can not be switched 2 2 2Target temp setting Clice t...

Страница 13: ...on the time Settings button interface displays as follows Click the value to set time directly the click confirm button to save the Settings For example setup time the 30 11 2016 16 00 00 input 30 11 16 16 00 00 the time change then click confirm button Note if the input format is not correct the wrong time will be saved by clicking confirm button ...

Страница 14: ...Click this button to start or end timing start setting function Timing on setting Click to set start time of the timing Timing end button Open red End gray Click this button to start or end timing end setting function Timing off setting Click to set end time of the timing For example above without action 0 o clock and 1o clock will be the on and off time of timing settings ...

Страница 15: ... timing setting Click the silent setting button and the interface displays as follows 2 4 1 The silent button Click the silent button the unit will enter the silent mode and interface displays as follows Click the silent button again to exit the silent mode ...

Страница 16: ...ent start time Click this button to set the timing silent start time Timing silent end time Click this button to set the timing silent end time Start time and end time setting value must be among the range of 0 00 23 00 and setting value can be precise to hour digit For example above click ON to use timing silent the unit will start the silent at 0 00 points and end at 4 00 click OFF to unuse the ...

Страница 17: ... themain interface will display static if you check the failurerecord the main interface will displays static Failure record is in reverse order according to the happening time Press the Clean key you can delete the fault record 4 2 6 Color Display Calibration Keep click quickly at the blank area on any interface till you hear a long beep Then you will enter the calibration interface Click to star...

Страница 18: ...perature recording curve is as follows 2 7 2 Comp Frequency curve Temperature curve automatically updates every one hour and the curve record can be stored for 60 days Start from the latest curve saved time if power is off and curve data collecting time is less than one hour the data in this period will not be saved ...

Страница 19: ...n water system Check the pipe water flow and water pump Anti freezing Prot E07 Water flow is not enough Check the pipe water flow and whether water system is jammed or not Primary Anti freezing Prot E19 The ambient temp Is low Secondary Anti freezing Prot E29 The ambient temp Is low Water inlet and outlet temp E06 Water flow is not enough and low differential pressure Check the pipe water flow and...

Страница 20: ...voltage measurement Inv Sampling Volt F11 The input voltage sampling fault Check and adjust the current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Check the communication connection Input Over Cur F26 The equipment load is too large PFC fault F27 The PFC circuit protection Check the PFC switch tube short circuit or not IPM Over heating F15 The IPM module is overheat Check and adjus...

Страница 21: ...1 12V GND 485_B2 485_A2 12V 12V 485_A3 485_B3 GND 12V 5V 0 10V OUT PWM OUT PWM IN 0 5V IN AI12 50K AI DI11 AI DI10 AI DI09 AI DI08 AI DI07 AI DI06 AI DI05 AI DI04 AI DI03 AI DI02 AI DI01 GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND T 5AL 250V ...

Страница 22: ......

Страница 23: ...xchange as conserve energy The operation pressure of the refrigerant system should only be serviced by a certified technician Check the power supply and cable connection often Should the unit begin to operate abnormally switch it off and contact the qualified technician Discharge all water in the water pump and water system so that freezing of the water in the pump or water system does not occur Y...

Страница 24: ... RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for the use of harmful substances in electric and electronic devices 7 The unit CANNOT be installed near the flammable gas Once there is any leakage of the gas fire can be occur 8 Make sure that there is circuit breaker for the unit lack of circuit breaker can lead to electrical shock or fire 9 The heat pump loc...

Страница 25: ...50A 30mA less than 0 1 sec 186 224A 2x95mm2 95mm2 280A 30mA less than 0 1 sec 2 Three phase unit Nameplate maximum current Phase line Earth line MCB Creepage protector Signal line No more than 10A 3x1 5mm2 1 5mm2 20A 30mA less than 0 1 sec nx0 5mm2 10 16A 3x2 5mm2 2 5mm2 32A 30mA less than 0 1 sec 16 25A 3x4mm2 4mm2 40A 30mA less than 0 1 sec 25 32A 3x6mm2 6mm2 40A 30mA less than 0 1 sec 32 40A 3x...

Страница 26: ...Note ...

Страница 27: ......

Страница 28: ...20000 231607 sales fluidra com www astralpool com au Fluidra Group Australia Pty Ltd 219 Woodpark Road Smithfield N S W 2164 ABN 87 002 641 965 ...

Отзывы: