Flowserve UltraSwitch PMV DM Скачать руководство пользователя страница 1

USER INSTRUCTIONS

Installation

Operation

Maintenance

Experience In Motion

PMV DS/DM Ultraswitch™

Switch box

FCD PMENIM0020-03-A5 - 05/19

Содержание UltraSwitch PMV DM

Страница 1: ...USER INSTRUCTIONS Installation Operation Maintenance Experience In Motion PMV DS DM Ultraswitch Switch box FCD PMENIM0020 03 A5 05 19 ...

Страница 2: ...traSwitch nomenclature 5 5 5 DS DM UltraSwitch switch options 6 6 INSTALLATION 7 6 1 Wiring instructions 8 7 SWITCHES CERTIFIED 9 7 1 Installation in hazardous locations 9 7 2 Adjusting limit switches 9 7 3 Cam fine adjustment 10 7 4 Adjusting Visual Position Indicator 10 7 5 Dome 10 7 6 Analog feedback option specifications 10 7 7 Calibrating 4 20 mA transmitter 11 7 8 Remote Unit 11 8 DIMENSIONS...

Страница 3: ...nstallation requirements must be addressed Pay attention to personal protection clothing glas ses gloves when performing installation or service Use only Flowserve original spare parts to avoid invalidating certification All installation inspection and maintenance of the equipment should be performed by suitably trained personnel In addition for ATEX all installation inspection maintenance and rep...

Страница 4: ...CONSTRUCTION Housings Covers Powder epoxy painted Aluminum or Stainless Steel Shaft Stainless Steel Cams Splines Nylon Terminal Block Nylon Internal Brackets Nylon Aluminum or Stainless Steel All External Fasteners Stainless Steel All Internal Fasteners Stainless Steel Indicator Polycarbonate Polyurethane Label Polyester or Stainless Steel Product name and model code Warnings Year of manufacture M...

Страница 5: ...radome D 180 3 way Ultradome E 180 3 way Center blocked Ultradome F 120 Thru Divert Ultradome H Black Yellow Ultradome K Green Red with Ektar Ultradome R Reverse Red Open Green Close Ultradome F Qty of switches 0 0 switches Cam assembly for 2 x M1 only 2 2 switches 4 4 switches G Switch option see chapter x for switch options H Certificate 14 General Purpose 15 Atex ia 18 cCSA CSAus Ex d equivalen...

Страница 6: ...x Current 5 60 VDC NA Pepperl Fuchs NBN4 12GM40 E2 Inductive 3 wires PNP NO 10 30VDC ND Pepperl Fuchs NCB2 12GM40 Z1 Proximity inductive 2 wire DC NC NE Pepperl Fuchs NCB2 12GM35 N0 NAMUR with LED NC 8 2V NF Pepperl Fuchs NCN4 12GM35 N0 NAMUR with LED NC 8 2V NG Pepperl Fuchs NJ5 11 N G NAMUR NC 8 2V NK Pepperl Fuchs NCN4 12GM40 Z0 Proximity 2 wire DC NO 8 2V NM Pepperl Fuchs NJ2 11 SN G NAMUR NC ...

Страница 7: ...plications make sure to properly install a coupler between DS DM UltraSwitch and actuator Once the DS DM UltraSwitch is installed with fasteners loosely tightened stroke the actuator two or three times to align the bracket Then tighten all fasteners NOTE External mounting fasteners must not be allowed to bottom Select length of screws to allow at least one thread turn of clearance against bottom o...

Страница 8: ...ed as standard Wire the solenoid to auxiliary terminals then connect power leads to the opposite terminal side Be sure to properly ground the solenoid at provided ground terminals DS DM UltraSwitch DS Series enclosures include two 3 4 NPT conduit cable entries and the DM Series include two M25x1 5 conduit cable entries Caution Proper and suitable conduit plugs must be instal led in unused conduit ...

Страница 9: ...cam s associated with CW as follows 1 Push or pull cam against spring to disengage it from splines 2 Rotate cam CW breaking contact with switch or moving magnet away from switch 3 Continue rotating cam CW just until switch trips 4 Release cam and re engage it with splines Rotate actuator valve to full counter clockwise CCW position Adjust cam s associated with CCW as des cribed in steps 1 through ...

Страница 10: ...ed with a visual indicator located beneath the housing This ring type indicator can easily be adjusted using manual force Simply rotate the indicator by hand to the desired position Double check that its position corresponds to the position of the valve Mounting instructions are included in the box 7 5 DOME As an option the DS DM UltraSwitch can be aquip ped with a red green dome on top The dome c...

Страница 11: ... feedback board span trim pot to yield 20 mA Turning CW increases value turning CCW decreases value 6 The zero and span adjustments are interactive Repeat steps 1 through 5 as necessary Note If transmitter adjustment gets difficult i e trim pots do not have desired effect start again by cente ring the trim pots This is accomplished by turning in one direction for 20 turns and reversing direction f...

Страница 12: ... 6 614 125 4 213 95 3 740 100 3 937 Clearence 118 4 646 D WITH NUT LINEAR NAMUR VDI VDE 3845 NAF TURNEX DOUBLE D 1 4 SHAFTS 3 4 14 NPT OR M25X1 5 1 3x 149 5 866 4 157 5 16 18 UNC 4X 35 4 1 394 57 2 2 252 35 4 1 394 57 2 2 252 M6 4X 56 590 15 2 203 21 827 FCD PMENIM0020 03 A5 05 19 ...

Страница 13: ...13 9 NOTES FCD PMENIM0020 03 A5 05 19 ...

Страница 14: ...14 9 NOTES CONTINUED FCD PMENIM0020 03 A5 05 19 ...

Страница 15: ...15 9 NOTES CONTINUED FCD PMENIM0020 03 A5 05 19 ...

Страница 16: ...roduct Because Flowserve is continually improving and upgrading its product design the specifications dimensions and information contained herein are subject to change without notice Should any question arise concerning these provisions the purchaser user should contact Flowserve Corporation at any one of its worldwide operations or offices For more information about Flowserve Corporation contact ...

Отзывы: