27.5 Replacing a Main Board
Removal
1
Make sure the valve is bypassed or in a safe
condition.
2
Disconnect the power and air to the positioner.
3
Remove the outer cover.
4
Remove the inner cover. See Figure 34: Inner Cover
below.
5
Disconnect the power cable to the main board.
6
Disconnect the auxiliary card cable if present. See
Figure 30.
7
Remove the inner cover by removing the 3 retaining
screws. See Figure 34.
8
Unplug the pressure sensor board connector from the
main board. See Figure 37.
9
Remove the screw from the main circuit board. See
Figure 35.
10
Gently lift the main board rotating the top up while
keeping the bottom in place.
Disconnect the hall sensor cable, the piezo cable, current
source cable and the feedback pot cable. (Use a small flat
screwdriver to pry the locking features and carefully
separate the connector from the main board. Be careful
not to pull the cable, as this may cause damage to the
cable.) See Figure 36.
Figure 35: Inner Cover
Installation
1
Place the main board over the positioner base.
2
Lift the main board rotating the top upwards while
keeping the bottom in place.
3
Plug in the hall sensor cable, the piezo cable, current
source cable and the feedback pot cable into the main
board. Ensure the connectors’ locking features
engage.
4
Place the main board on the positioner base.
5
Connect the pressure sensor board cable on to the
main board.
6
Reinstall the main board screw.
7
Replace the inner cover by reinstalling the 3 retaining
screws.
8
Reconnect power.
9
Calibrate.
Figure 36: Main Board Screw
27.6 Replacing the Pressure Sensor
Board
Removal
1
Make sure valve is bypassed or in a safe condition.
2
Disconnect power and air to the positioner.
3
Remove plastic inner cover.
4
Unplug pressure sensor from the main board.
5
Unscrew the 4 screws holding the pressure sensor
board in place. See
Error! Reference source not
found.
37.
6
Remove the pressure sensor board.
Installation
1
Place the pressure sensor O-rings in the three holes.
2
Cover the O-rings with the pressure sensor board.
3
Insert the 4 screws. Tighten until the pressure sensor
board makes firm contact with the base.
4
Plug the pressure sensor cable back into the main
board.
5
Reinstall the plastic inner cover.
Calibration
1
Initiate a Pressure or Triple Calibration from the DTM.
Feedback
Pot
Connector
Piezo
Connector
Hall
Sensor
Connector
Main
Board
Screw
Inner
Cover
Screws
Current
Source
Auxiliary
Card
Screw
(optional)
Figure 34: Main Board Connectors