FlowCon GreEQ Скачать руководство пользователя страница 1

Installation and Operation Instruction

Figure 1

A

B

C

D1

D2

E

E

C

F

Turn to 
setting 
1.0

Turn to

higher

settings

The 

FlowCon GreEQ - equal percentage - 

 

inserts are for use with three different FlowCon 
valve housings, either:

 

FlowCon A DN15-25 (1/2”-1”)

 

FlowCon AB DN15-32 (1/2”-1 1/4”)

 

FlowCon ABV DN15-40 (1/2”-1 1/2”)

Insert Setting and Installation

Prior to installing the FlowCon GreEQ insert 
(supplied from factory in setting 5.0 due to cali-
bration), the system should be properly flushed. 
Blank valve covers are available to be installed 
during flushing.

It is recommended to grease the O-rings located 
around the insert and headnut with silicone grease 
before installing the insert in the valve housing. 

The desired flow rate is set by ad-
justing the insert (turn counter-clock- 
wise to setting 1.0 and then clock-
wise up) with a special adjustment 
key. 

Range is between 1.0 and 5.0 

Do not overturn.

 Scale setting is 

located on top of the insert. The large 
white digits, numbered 1 to 5, indica- 
te full turns and red digits, numbered 
0 to 9, indicate 1/10 of full turn. Flow  
setting may be done either before or 
after the insert is installed in the 
valve housing. Once flow is set and 
insert is fitted in the valve housing, 
the required actuator may be applied. Please 
see specific installation instruction for selected 
actuator.

General Assembly Drawing 
FlowCon GreEQ

A:  Valve housing
B:  GreEQ insert 
C:  Adjustment keys
D1:  P/t plug (2 pcs.)
D2:  Plug (2 pcs.)
E:  Union end connections
F:  FlowCon actuator

FlowCon GreEQ 15-40 mm (1/2”-1 1/2”)

1B95093 - 01/2022

This paper is a supplement to the

 FlowCon General Instruction 

Latest release of any FlowCon material is available on

 

www.flowcon.com

Page 1 of 2