www.flowair.com
HMI MANUAL
9
ENGLISH
POL
SKI
РУ
ССК
ИЙ
Menu
setting Option
Value
1
Temperature
calibration
–9°C ~ +9°C
2
Fan status
C1: Thermostatic mode
C2: Continuous mode
3
Temperature
sensor
0: Internal Sensor
1: External Sensor NTC
4
Antifreeze
0: Off
1: On
5
Antifreeze
+5°C ~ +10°C
6
Modbus ID setting
1~247( 01~F7)
5.2 Button lock/unlock
• To LOCK all buttons press and hold + and then – buttons for
5 seconds.
• To UNLOCK all buttons press and hold + and then – buttons for
5 seconds.
5.3 Clock setting
• When HMI controller is turned off, press and hold FAN button for
3 seconds and enter into time clock setting.
• Option sequence as follows: hour, minute weekday.
• To change option use FAN button.
• To change value use + and – buttons.