Flo i-Controller Скачать руководство пользователя страница 8

 

Installation Guide

 

IN-IC1-15

 

Title

:

 

Jace to i-Controller REV.200 MPU (575V 40–70 Ton) Conversion

 

 

Flō 

Tech Support 888-598-1198 

8

 

4-6DEC2021 

 

 

Existing 

Points 

Expansion Module B 

Expansion B 

Pin # 

NEW 

24 VAC Transformer Power 2 - 

1* 

24 VAC Transformer Power 2 + 

9* 

Suction Press Comp 3 SG WHT  

Suction Press Comp 3 0V BLK 

15* 

Suction Press Comp 3 Pwr RED 

16* 

Discharge Press Comp 3 SG WHT 

Discharge Press Comp 3 0V BLK 

15* 

Discharge Press Comp 3 Pwr RED  

16* 

Suction Press Comp 4 SG WHT  

Suction Press Comp 4 0V BLK 

15* 

Suction Press Comp 4 Pwr RED  

16* 

Discharge Press Comp 4 SG WHT 

Discharge Press Comp 4 0V BLK  

15* 

Discharge Press Comp 4 Pwr RED  

16* 

Space Temperature 2 SG 

24 

Space Temperature 2 0V 

28* 

Space Humidity 2 SG 

Space Humidity 2 0V 

15* 

Space Humidity 2 Power 

Reheat/Reclaim Inlet Probe 2 SG 

29 

Reheat/Reclaim Inlet Probe 2 0V 

28* 

*

This indicates that you will be attaching to a 10” wire, not a pin.

 

**This indicates that you will be attaching to the CSTB1. 

Table 3. Input Conversion Table 

 

7.7

 

Wire

 

Analog Output  

Wire analog outputs based on table 4. 
 

Existing 

Points 

i-Controller 

i-Controller 

Pin # 

See Wiring 

Diagram  

in Unit

 

Outside Air Damper SG 

21 

Outside Air Damper 0V 

25* 

Return Air Damper SG 

22 

Return Air Damper 0V 

25* 

Bypass Air Damper SG 

23 

Bypass Air Damper 0V 

25* 

VFD SG 

24 

VFD 0V 

25* 

Digital Compressor 1 SG 

26 

Digital Compressor 1 0V 

25* 

Modulated Reheat SG 

27 

Modulated Reheat 0V 

25* 

New 

CSTB -24VAC Black 

28* 

CSTB +24VAC Red 

29* 

 

Existing 

Points 

Expansion Module B 

Expansion B  

Pin # 

See Wiring 

Diagram  

in Unit

 

Digital Compressor 2 SG 

21 

Digital Compressor 2 0V 

20 

 

*This indicates that you will be attaching to a 10” wire, not a pin.

 If 

multiple CSTB’s, use the CSTB that powers the actuators.

 

Table 4. Analog Output Conversion Table 

 

 

Содержание i-Controller

Страница 1: ...oat Switch 4 6 5 Install New CO2 Sensor 5 6 6 Install Space Temp RH Combo Sensor 5 7 Install The i Controller Components 6 7 1 Remove Existing Jenesys Controls 6 7 2 Install New i Controller and Expan...

Страница 2: ...rols Screwdriver Step Drill Bit for CO2 Sensor Probe Installation Refrigerant Tee with Schrader Depressor 2 Schrader Cores 4 Conductor Shielded Twisted Wire or Equivalent 5 Conductor Shielded Twisted...

Страница 3: ...gths of Black 18 AWG wire to the following i Controller green plug connection points 1 7 8 25 28 61 See Figure 1 for plug orientation Attach 10 lengths of Red 18 AWG wire to the following i Controller...

Страница 4: ...the 0 667 PSI Discharge transducers on the liquid lines of circuits 1 2 3 4 If there are spare service ports on the unit install the transducers on a spare service port If spare service ports are not...

Страница 5: ...w Figure 3 CO2 sensor location inside the unit Wire the new CO2 based on the following see Figure 4 24VAC Red wire 24VAC Black wire COM Green wire CO2 SIGNAL White wire NOTE Do not wire the CO2 sensor...

Страница 6: ...1 down 2 up 3 down 4 down NOTE The actual switch may be white but for illustrative purposes the switch is black in the Figure 6 below Figure 6 Fl i Controller Expansion Addressing Wire the 2 expansion...

Страница 7: ...Comp 1 SG WHT 12 Discharge Press Comp 1 0V BLK 8 Discharge Press Comp 1 Pwr RED 15 Suction Press Comp 2 SG WHT 13 Suction Press Comp 2 0V BLK 8 Suction Press Comp 2 Pwr RED 15 Discharge Press Comp 2...

Страница 8: ...Reheat Reclaim Inlet Probe 2 SG 29 Reheat Reclaim Inlet Probe 2 0V 28 This indicates that you will be attaching to a 10 wire not a pin This indicates that you will be attaching to the CSTB1 Table 3 In...

Страница 9: ...aim do not wire 24VAC to point 86 The dry common from the refrigeration rack reclaim control is connected to point 86 Existing Points Expansion Module A Expansion A Pin See Wiring Diagram in Unit ERV...

Страница 10: ...With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the and set the value Press ENTER a second time to accept changes The controller will au...

Страница 11: ...hen press ENTER Dehumidification mode is now turned OFF 9 6 Heating Test Mode From the Field Technician Options screen press T2 Test Modes Press T3 2 Operational Tests Use to navigate to the Heat Test...

Страница 12: ...ions button Using the to navigate to the value that you wish to change With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the set the value...

Страница 13: ...l Tech Support 888 598 1198 13 4 6DEC2021 11 Appendix 11 1 i Controller Layout 1 24VAC Power Point 9 and 1 2 Analog Inputs 3 Digital Inputs 4 Digital Outputs 5 Analog Outputs 11 2 Expansion Board Layo...

Отзывы: