Technical Guide 

 

CN-IC2-15

 

Title

:

 

i-Controller 2.0 BACnet Communication Settings

 

 

EXTERNAL

  

1-22AUG2022 

Overview 

 

For proper data transfer to occur between the Building Management System (BMS) and the Fl

ō

 i-Controller 2.0, the BACnet 

communication connection must be properly configured.   If the two controllers are not communicating and if the BMS 
Communication 

Status displays ‘Offline’ in the 

BMS Status screen of the i-Controller, verify the following information. 

 

CAUTION

: Before connection, ensure there is no earth ground on the wires used for the RS485 connection. 

Do not ground any of the wires connected to the RS485 terminal blocks inside the unit.  Doing so will result in damage to 
the i-Controller hardware. 
 

i-Controller 2.0 BACnet Network Configuration 

 
Verify the i-Controller protocol, address, and baud rate. 
 

 

 

Figure 1. i-Controller BMS Status screen 

 

The “

BMS Status

” screen displays the 

current Fl

ō

 i-Controller BMS protocol, BACnet address, baud rate and the status of 

the connection to the BMS.  If the Fl

ō

 i-Controller is connected, the BMS status will display 

“Online”

. The BMS status will 

display 

“Offline” if the BMS is offline or the 

Fl

ō

 i-Controller is not connected or properly configured.  

 
To change the communications protocol, address, perform the following steps: 
 

1.

 

From the Home Screen, press the program   button three times to navigate to the settings menu. 

2.

 

Use the down arrow   button to 

highlight “Communications” and press 

enter   button twice to navigate to the 

BMS Configuration Screen. 

3.

 

 On BMS Connectivity page 1, you can set the controller address and baud rate. 

4.

 

Use the enter   button to navigate to the address field. 

5.

 

Using the   and   buttons increase and decrease the value as desired. 

6.

 

Once the desired value has been reached press the

 enter 

 button to set the value. 

7.

 

On BMS Connectivity page 2, you can set the communication protocol. 

8.

 

With the cursor back in the home position, at top right of screen, Use the down arrow   button to navigate to 

page2. 

9.

 

 Use the enter   button to navigate to the value that you wish to change. 

i-Controller 2.0 Settings 

 

BMS Protocol:  

BACNET

 

Address:  

xx

 

Baud rate:  

38400

 

 
BMS COMM STAT: 

Online

 