Technical Guide
CN-IC1-12
Title
:
i-Controller Visograph Navigation REV.201.05
EXTERNAL
37
1-5JULY2021
Overrides
If the i-Controller is connected to a BMS, remove RS485
connection before proceeding with Overrides.
Before proceeding to the override options, please note
that the overrides are not timed and must be manually
removed once your task is complete. All overrides will be
reset in the event of a power cycle.
1.
To access the Override menu, press T2 on the Field
Tech Options Menu to access the Test Modes
Menu.
2.
From the Test Modes menu, press T6 and T7
simultaneously to access the QA Options.
3.
Then press T2, T3, or T4 to access the Override
options.
Figure 1034. Field Tech Options screen
Figure 1045. Test Modes screen
Figure 1056. QA Options screen
T1: Go to Test Mode Menu
T2: Go to Input Overrides
T3: Go to Output Overrides
T4: Go to Other Overrides
T5: Go to I/O Status
T8: Go to Field Tech Menu
Input Overrides:
Figure 1067. Input Overrides screen 1
T1: Go to QA Options
T2: Go to Output Overrides
T3: Go to Other Overrides
T4: Increase
T5: Enter
T6: Decrease
T7: Previous Page
T8: Next Page