Safety & Installation Guide
Version: 01.12
Valid from 22.10.2018
FG2P1-4S1P00/1
9
This manual
applies only on Flisom’s eFlex Series modules
3.5.3
Module arrangement recommendation
All lanes of modules should be positioned parallel and should have enough space between for thermal
expansion (ca. 2 mm). Provide sufficient space between the module lanes to ensure that there are
walk ways, between the modules, so that there is no walking on the eFlex modules. Leave enough
space between module strings for the cable duct. Check that the cable duct is not shading the
modules. Cover the Junction box with the cable duct system for additional UV protection.
3.5.4
Roof Application
According to the ADCO PVA 600BT tape application guideline the protective foil has to be removed
immediately prior to applying. Avoid contaminating the adhesive. The substrate has to be placed within
30 minutes after any primer has been applied. Best application temperature for the PVA 600BT is
10°C to 50°C.
Application Steps:
1. Mark the module position on the roof.
walking way
wal
k
ing
wa
y
Fig. 5: arrangement eFlex