6.5 Mode 5: Packing / Bagging
Typical Applications
•
Packing and Bag filling machines.
•
Weighing of additives in tank or hopper.
Operation
•
The container is filled up to target value
accurately as 2 speeds.
•
It is emptied totally by applying emptying input.
•
Process ends when the weight goes into
[
Zero_r
] after emptying.
Mode Related Filling Parameters
The mode related filling parameters shall be entered before start up the filling. Please enter the values
below carefully for better filling performance of the filling machine.
Display
Operation
[
123.456
kg ]
Press long
key, [
Zero_r
] message appears.
[
Zero_r ]
[ XXXXX ]
Zero range.
This parameter has two functions;
1. At filling start: To start feeding, the weight indication has to be
in Zero Range.
2. At Emptying: If the weigh is decreased in this range, the scale
is accepted empty and the gate is closed.
Enter zero range value by pressing
and
keys. Press
the
key to go to the next parameter.
[
d_dıSC ]
[ X.X ]
End of emptying delay.
After the weight value goes into zero
range at emptying, [
d_d
ıSC
] parameter delays closing the gate
for completely emptying.
Enter the value by pressing
and
keys. Press the
key to go to the next parameter.
Maximum value is 9.9 seconds. Default is 0.0 seconds.
[
d_GAtE ]
[ X.X ]
Gate control delay.
This parameter has two functions;
1. If there is no gate switch (GAT_Ch = 0), this time delays
"End of emptying" output.
2. If there is a gate switch (GAT_Ch = 1 ), this time delays to
check the gate position.
Enter gate control delay value by pressing
and
keys.
Press the
key to go to the next parameter.
Maximum value is 9.9 seconds. Default is 0.0 seconds.
[
GAT_Ch ]
[ X ]
Gate position check
0 = No gate switch
1 = Gate switch function is enable
Enter gate position check value by pressing
and
keys.
Press the
key to go back to the operation.
Default is “0”.
Note:
For
TARGET
and
TOLERANCE
entry please see section 7, page 69