FT-10 Fill Technical Manual, Rev. 2.21, July 2020
Page 112 of 131
17.
CC-L
INK
(
ONLY
FT-10
FILL
CC)
After setting related parameters to can communicate with the indicator via CC-Link network. Supported CC-
Link version is v1.10 and baud rates are 156 kbps (default), 625 kbps, 2,5 Mbps, 5 Mbps and 10 Mbps.
[07-] CC-Link
(Only FT-10CO, CC)
This sub-block includes the parameters related with the CC-Link interfaces of FT-10 FILL indicator.
[070 0] Data Format
0 : Signed 32 bit integer, no decimal point implied
1 : 32 bit float, decimal point implied
[071 000] Rack Address
The CANopen rack address of FT-10 will be entered via keypad between 001 to 126.
[072 000] Baudrate
0 : 156kbps
1 : 625kbps
2 : 2.5kbps
3 : 5Mbps
4 : 10Mbps
There are 2 LED’s near the CC-Link connector which are;
NS Run LED
State
Indication
Off
No network participation, timeout status (no power)
Green
Participating, normal operation
Red
Major fault (FATAL error)
MS Error LED
State
Indication
Off
No error detected (no power)
Red
Major fault (Exception or FATAL event)
Red, flickering
CRC error (temporary flickering)
Red, flashing
Station Number or Baud rate has changed since startup (flashing)
In the case of red LED warning, check cabling and configuration before reenergizing the instrument after 30
seconds power off.
17.1 Data Format
Data format of weight value can be programmable for Floating point (IEEE 754) or Integer. Refer to
parameter [070].
1
NS RUN LED
2
MS ERR LED
3
CC-Link interface