webdyn.com
V2.0 subject to changes | Webdyn © by Flexitron Group
35
3.1.1.4 RESET
The WebdynEasy W M-Bus has 2 RESET functions that can be triggered using the RESET button (see
section 2.4.4.2.: “RESET button).
• RESTART of the product.
•
Hard RESET of the product configuration.
In case of factory pre-configuration of custom settings, these are considered as the default settings and
therefore applied when using a factory reset mechanism.
To find out if the WebdynEasy has a customer configuration, please check the commercial
reference of the product. (see chapter 2.2.2: Identification.
3.1.2 Application Operation
In RUN mode, the product carries out 3 tasks which are:
• WM-BUS.
• Modem.
• Monitoring.
These tasks are regular and not synchronised with each other.
3.1.2.1 WM-BUS Task
The WM-BUS task is used to collect WM-BUS data from the sensors. It has its own scheduler to set its run
frequency, date and time. Listening time can also be configured in the WM-BUS task.
Frame recording principle:
During a WM-Bus listening window, only the first frame of each size sent by a module is recorded.
Example: When a meter emits a 20 byte frame every 8 seconds and a 45 byte frame every 60 seconds.
During a 2 minute listening window, only the first 20-byte frame and the first 45-byte frame are recorded.
3.1.2.2 Modem Task (connection to the IS)
The Modem task is used to:
• Set the hub time using NTP.
•
Upload and download files to and from the FTP server.
It has its own scheduler to set its run frequency, date and time. The type of file to be uploaded to the
server can also be configured.