28
OK
RESET
AIR ERROR
>> RESET
The display shows a lack of air.
This error can appear if the tubes of pressure switch are
disconnected or obstructed or if the connection of air
combustion or fumes is obstructed. The error can also appear
if the exhaust fan or differential pressure sensor is defective.
To reset the error, press RESET
EXHAUST FAN ERR.
>> RESET
The display shows that the extractor does not work or is
disconnected.
Check the connection of the cable or check the good rotation
when the exhaust fan starts. If the exhaust fan does not rotate,
replace it.
To reset the error, press RESET
BRUNER ERROR
>> RESET
The display shows a default on the burner control device which
is located on the rear side of the control board plate.
The error can be linked to different problems.
CONDENSATE
ERROR
The display does not concern ATX range.
If this message is displayed on ATX model, check the
connector shunt of condensate level sensor, because this
model does not have float.
To reset the error, press RESET
SYSTEM
ERROR
The display shows a system default on the control board.
Replace and configure the new control board.
OK
RESET
OK
RESET
OK
RESET
OK
RESET