7– TROUBLESHOUTING
WARNING : The power supply and gas supply must be cut before any intervention on the heater.
7.1 List of defect and solutions to problems
OVERHEATING
ERROR
The display shows that the safety thermostat with manual reset
is in default. Press the button of the thermostat.
The error can come from a power failure whereas the heater
was operating or because of a fan short-circuit. The default can
also come from a faulty components: fan condenser,
thermostat with manual reset, control board.
SENSOR P AIR
ERROR
The display shows that the differential pressure sensor is
disconnected or defective.
Check the connection or replace the pressure sensor.
AIR SENSOR
ERROR
The display shows that the blowing air temperature sensor is
disconnected or defective.
Check the connection or replace the air temperature sensor.
FUMES SENSOR
ERROR
The display shows that the fumes sensor is disconnected or
defective.
Check the connection or replace the fumes sensor located
under the exhaust fan.
PH/N INVERSION
ERROR
The display show a polarity reversal.
It is necessary to cut-off the power supply of the heater and
reverse the phase and neutral of the main power supply of
the heater. When the operation is complete, the message on
the display will disappear.