The heaters can be switched ON/OFF manually using a suitable double pole switch to provide localised heating. 
However for optimum temperature control we recommend using a suitable room thermostat. For advice please 
contact your distributor.

  

DESCRIPTION & SPECIFICATION

CR radiant heaters are designed to provide primary, localised or perimeter heating in residential, commercial and 
industrial buildings. For optimum performance the heaters should be installed between 2.4m and 3.5m above floor 
level either by direct ceiling mounting using the optional bracket (CRB), laid into a standard 24mm “T” section 
suspended ceiling grid or suspended from the ceiling using suitable chains or wires.

  

Model

3CR

6CR

Power

300W

600W

Voltage

230V~

230V~

Current

1.3A

2.6A

Dimensions (L x W x H)

595 x 595 x 25mm

1195 x 595 x 25mm

Weight

6.2kg

11.9kg

Minimum installation height

1.8m

1.8m

Recommended installation height

2.4 - 3.5m

2.4 - 3.5m

IP rating

IP 55

IP 55

IMPORTANT:

 READ CAREFULLY BEFORE USE AND KEEP FOR FUTURE REFERENCE.

Ÿ

Do not install the heater directly below electrical outlets when using the optional ceiling mounting bracket. 

Ÿ

CAUTION — Some parts of this product can become very hot and cause burns. Particular attention has 
to be given where children and vulnerable people are present.

Ÿ

Check the heater for damage before installation. If the supply cord is damaged, it must be replaced by the 
manufacturer or it’s service agent.

Ÿ

This heater must not be used in ambient temperatures exceeding 30°C.

Ÿ

This heater is a Class I appliance and to comply with the Wiring Regulations it must be earthed. 

Ÿ

The surface of the panel can be cleaned using a soft cloth and a mild aqueous mild detergent. The heater must 
be switched off, allowed to cool and isolated from the electrical supply before cleaning.

Ÿ

The heater must be installed by a qualified electrician in accordance with current wiring regulations. The 
heating must be connected to the fixed wiring and protected by 30mA residual current device (RCD) and a 
suitable fuse or circuit breaker. 

Ÿ

Do not use in hazardous areas. 

Ÿ

The heater must be connected to a circuit with means for disconnection from the supply having contact 
separation of at least 3mm in all poles.

Ÿ

The ceiling surface must be capable of supporting the weight of the heater. If in doubt please check.

Ÿ

The heater must not be installed at a height less than 1.8m from the floor. 

  

SAFETY INSTRUCTIONS

Ÿ

WARNING

: This heater is not equipped with a device to control the room temperature. Do not use this heater in 

small rooms when they are occupied by persons not capable of leaving the room on their own, unless constant 
supervision is provided.

Ÿ

Children of less than 3 years should be kept away unless continuously supervised. Children aged from 3 years 
and less than 8 years shall only switch on/off the appliance provided that it has been placed or installed in its 
intended normal operating position and they have been given supervision or instruction concerning use of the 
appliance in a safe way and understand the hazards involved. Children aged from 3 years and less than 8 
years shall not plug in, regulate and clean the appliance or perform user maintenance.

CR Radiant Ceiling Panel Heaters

Installation and User Instructions