VESDA-E VEU-A10 Product Guide
56
www.xtralis.com
5.3
Security
The VEU-A10 has two levels of protection against unauthorized access. For connection via Ethernet or WiFi,
a password of at least 8 characters must be used. After connection, a four digit PIN is used to control the
access level.
5.3.1
WiFi and Ethernet Authentication
A password is used to authenticate access over Ethernet or WiFi connection when using Xtralis VSC.
The password is set in the General options tab for the VEU-A10 detector, and applies to both Ethernet and
WiFi access. Refer to Section 5.5.3 on page 62 and Section 5.5.4 on page 64 for further information. When
creating connection profiles in Xtralis VSC, the same password must be entered. Refer to Section 5.1.2 on
page 49 for further information.
The password must conform to the following rules:
l
8 or more characters.
l
Contains one or more numeric characters.
l
Contains both upper case and lower case characters.
5.3.2
Access Control
When accessing the VEU-A10 detector via Xtralis VSC, user functionality is initially limited. For additional
privileges, the user must log in to the detector using an 4 digit numeric PIN code. In Xtralis VSC, select Logon
from the Connection menu and enter the PIN.
User Level
Access Level
Functional Authorization
USR
Low
This is the USER or the OPERATOR level. The user can view
the event log and change the date and time. They can also
perform selected zone control functions.
ADM
High
At the ADMINISTRATOR level access is available to most
functions. These include setting alarm thresholds, normalizing
air flows, reset filter, and defining the relay configuration.
DST
Absolute
The DISTRIBUTOR level allows unlimited access to all the
system commands and parameters.
Table 5-1: User Access Levels
The default PIN for each level of user is set at the factory. The distributor has access to the PINs for each
level. PIN numbers are disclosed to authorized personnel attending accredited training courses.
After logging in the user has the option to change the default PIN. To guard against unauthorized access, if
someone enters an incorrect PIN number three times they will not be allowed another attempt for ten minutes.
5.3.3
Product Security Advice
Warning:
Failure to comply with the requirements below exposes the system to malicious interference
which could disable smoke reporting.
Commissioning Requirements
l
All VESDAnet wiring and connection ports must be secured against unauthorized access.
l
Ethernet and Wi-Fi ports must ONLY be connected to networks which are secure and physically or
logically separate from business IT infrastructure.
l
VESDA devices including HLIs must not be accessible from the Internet. Any provision of remote
access to VESDA devices must be subjected to a full cyber security risk assessment and regular
review.
l
WPA-2 encryption must be used whenever Wi-Fi is enabled.
l
Restrict access to HLI devices to authorized personnel only.
Содержание VESDA-E VEU-A10
Страница 1: ...VESDA E VEU A10 Product Guide November 2018 Document 22077_12 Part Number 30334 ...
Страница 2: ......
Страница 10: ...VESDA E VEU A10 Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VEU A10 Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEU A10 Product Guide 48 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VEU A10 Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 100: ...VESDA E VEU A10 Product Guide 94 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 106: ...VESDA E VEU A10 Product Guide 100 www xtralis com This page is intentionally left blank ...
Страница 110: ...VESDA E VEU A10 Product Guide 104 www xtralis com This page is intentionally left blank ...
Страница 116: ...VESDA E VEU A10 Product Guide 110 www xtralis com Z zone 59 61 79 105 ...