OPERATING INSTRUCTIONS MANUAL 

(Please retain for future reference) 

 

For 

 

F-400T DUAL FUEL CONSTRUCTION HEATER 

 
 
 

 

 

CERTIFIED FOR USE IN CANADA AND U.S.A. 

As per Standard ANSI Z83.7 2000/ 

CSA 2.14 2000 Gas Fired Construction Heaters Unvented/Unattended Type.

 

 
 

 

 

FLAGRO INDUSTRIES LIMITED 

ST. CATHARNIES, ONTARIO 

CANADA 

 
 

 
 

Содержание F-400T

Страница 1: ...ture reference For F 400T DUAL FUEL CONSTRUCTION HEATER CERTIFIED FOR USE IN CANADA AND U S A As per Standard ANSI Z83 7 2000 CSA 2 14 2000 Gas Fired Construction Heaters Unvented Unattended Type FLAG...

Страница 2: ...SION HAZARD KEEP SOLID COMBUSTIBLES SUCH AS BUILDING MATERIALS PAPER OR CARDBOARD A SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY...

Страница 3: ...YOU HAVE QUESTIONS ABOUT APPLICATIONS Other standards govern the use of fuel gases and heat producing products in specific applications Your local authority can advise you about these SPECIFICATIONS...

Страница 4: ...apor withdrawal only 1 All cylinder connections must be made using a wrench to tighten the POL fitting 2 Be sure that the cylinder valve is in the closed position when connection or disconnecting the...

Страница 5: ...depending on the fuel being used A fuel selector valve is located on the manifold of the heater Ensure that this valve is in the proper position depending on the fuel being used DO NOT operate the he...

Страница 6: ...into operation The replacement hose assembly shall be that specified by the manufacturer 3 The appliance must be kept clear and free from combustible materials gasoline and other flammable vapors and...

Страница 7: ...4 Open all gas supply valves 5 Depress the main switch to the START position The fan will start and the burner should ignite 6 Set the Thermostat to the desired temperature 7 If heater fails to ignit...

Страница 8: ...urn counter clockwise to decrease sensitivity POSSIBLE CAUSE Blockage in copper inlet tubes REMEDY Disconnect tubes from air switch Use high pressure air to clean any debris that my block the airflow...

Страница 9: ...sures are supplied to the heater see approval label POSSIBLE CAUSE Spark Plug REMEDY Ensure gap in spark plug is approx 3 16 Check spark plug wire connections Ensure spark plug has good spark Replace...

Страница 10: ...rd POSSIBLE CAUSE Thermostat REMEDY Ensure the thermostat is calling for heat POSSIBLE CAUSE Electrical All components REMEDY Before replacing an component all connections must be checked to ensure el...

Страница 11: ...UEL SELECTOR VALVE S 403 IGNITOR S 408A FAN BLADE S 401 PRESSURE ADJUSTMENT CAP FOR S 402 REG S 402C REGULATOR 1 2 PSI S 402 S S FILTER SCREEN S 402FS SOLENOID VALVE COVER 200871 002 FLAME ROD S 406A...

Страница 12: ...HARNESS S 415W IGNITION BOARD S 415P MAIN RELAY S 412 AIR PROVEN SWITCH S 414 THERMOSTAT S 416 FRONT LEG S 418 REAR SCREEN S 419 6 RUBBER WHEELS S 420 PIPE CLAMP S 423 AIR SENSING TUBES S 427 POWER CO...

Страница 13: ...IT S 411 OFF RUN START SWITCH S 412 MAIN RELAY S 414 AIR PROVING SWITCH S 415P POTTED IGNITION CONTROL 120V 2002 TO CURRENT S 416 THERMOSTAT WK 400 WHEEL KIT S 418 FRONT LEGS S 419 SCREEN S 420 RUBBER...

Страница 14: ...FLAME ROD SPARK PLUG FENWAL IGNITION BOARD GROUND F 400T WIRING DIAGRAM 2010 400T 202 F 400T WIRING DIAGRAM 2010 Note If any of the origional wire as supplied with the appliance must be replaced it mu...