Fisher FIELDVUE DVC6200 Скачать руководство пользователя страница 1

 

DVC6200 Digital Valve Controller  

on 1061 Size 80-100 Actuator 

(Window Mount)

 

 

Use these instructions to mount a Fisher

®

 

FIELDVUE™ 

DVC6200 digital valve 

controller

 on Fisher 1061, size 

80-100 actuator. 
 

 

 

Avoid personal injury or property damage from 
sudden release of process pressure or bursting of 
parts. Before performing any installation 
operations: 

 

 

 

Always wear protective clothing, gloves, and 
eyewear.

 

 

Do not remove the actuator from the valve while 
the valve is still pressurized. 

 

 

Disconnect any operating lines providing air 
pressure, electric power, or a control signal to 
the actuator. Be sure the actuator cannot 
suddenly open or close the control valve. 

 

 

Use bypass valves or completely shut off the 
process to isolate the control valve from 
process pressure. Relieve process pressure 
from both sides of the control valve. 

 

 

Vent the pneumatic actuator loading pressure 
and relieve any actuator spring 
precompression. 

 

 

Use lock-out procedures to be sure that the 
above measures stay in effect while you work 
on the equipment. 

 

 

Check with your process or safety engineer for 
any additional measures that must be taken to 
protect against process media. 

 

 
Refer to figure 3 for mounting parts identification for 
1061 Size 80-100. Refer to the DVC6200 digital valve 
controller instruction manual for parts identification.  
Refer to the appropriate actuator instruction manual for 
actuator installation, operation, maintenance, and parts 
identification.  
 
1. Isolate the control valve from the process line 
pressure and release pressure from both sides of the 
valve body. Shut off all pressure lines to the actuator, 
releasing all pressure from actuator.  
 
Use lock-out procedures to be sure that the above 
measures stay in effect while you work on the 
equipment. 
 
 
 
 

 
2. Remove the cover plate screws and cover plate from 
the actuator, if present. 
 
3. Install the cam (key 1) on to the lever of the actuator. It 
is necessary for use of arced feedback mechanism. 
Consult with the appropriate actuator instruction manual 
for proper actuator disassembly and reassembly.  
 
4. Attach the cam (key 1) to the lever arm of the actuator 
using hex head cap screws (key 2). 
Ensure that the cam is oriented as shown in figure 3. 
 
5. Detach the roller assembly from the arced feedback 
arm. 
 
6. Refer to figure 2, attach the follower arm extension   
(key 3) to the arc feedback arm using hex head cap 
screws (key 4), lock spring washers (key 5) and hex nuts 
(key 6). 
 
7. Attach the roller assembly to the follower arm 
extension (key 3) as shown in figure 2. 
 
8. Attach the digital valve controller to the arced feedback 
assembly (key 7) as per the actuator requirement using 
hex socket cap screws (key 8). 
 
9. Attach the arced feedback assembly (key 3), along with 
the digital valve controller to the yoke of actuator using 
hex socket cap screws (key 9) as shown in figure 3.   
 
10. Ensure that the roller of arced feedback assembly is 
centered and resting on the cam surface.  
 
11. Make pneumatic and electrical connections to the 
digital valve controller as described in the digital valve 
controller instruction manual.  
 
12. It may be necessary to fine tune the placement of the 
cam so that the digital valve controller receives the proper 
feedback. 
 
13. Setup and calibrate the digital valve controller as 
described in the digital valve controller instruction manual 
or quick start guide.  
 
For additional information concerning mounting, setup, 
calibration, and maintenance of the DVC6200 digital 
valve controller, refer to the appropriate instruction 
manual.  
 
 
 
 
 

 
 
 

______________________________________________________________________________________________________ 
 

w

M

ww.Fisher.com 

 
 

 

ounting Instructions 

D103452X012 
May 2010 

 

 

Отзывы: