3 | Assembly
FISCHER Mess- und Regeltechnik GmbH
18
BA_EN_DE90
3.4.3 Device with Modbus
DANGER
Auxiliary for ATEX devices
When selecting the power supply, bear in mind that it may be a potential ignition
source.
Take suitable safety precautions to prevent this risk.
Modbus IN
Modbus OUT
1
2
Fig. 17:
Replacement plate Mod-
bus
The devices with a Modbus interface do not have analog and switch outputs.
The replacement board is equipped with a 5-pin M12 flange connector for the
Modbus input and with a 5-pin M12 flange socket for the Modbus output.
The DE90 is usually connected to the Modbus RTU network as a so-called
slave to the Modbus RTU network. Up to 247 devices can be addressed in one
line network.
NOTICE! Star-shaped networks are not allowed.
MASTER
DE90
1
2
DE90
1
2
DE90
1
2
Address 1
Address 2
Address 247
Bus termination
AC/DC
AC
M
Supply
1
2
E
Modbus
5
Fig. 18:
Modbus RTU network
Communication is effected solely with the Modbus master. The connected
slaves only react to direct commands from the master, which is why communic-
ation between the slaves is not possible.
To guarantee fault-free data transmission, we recommend terminating the end
point of the Modbus RTU network with a 120 Ω resistor. This bus termination
resistance is available as an accessory.
3.4.3.1 Connection to an existing Modbus RTU network
It can be connected to an existing Modbus network via a conventional T-piece
(passive TAP).
MASTER
M
TAP
M
Slave
TAP
LT
LT
M
Slave
TAP
DE90
1
2
Supply
1
2
E
AC/DC
AC
Fig. 19:
Modbus connection
Содержание PRO-LINE DE90
Страница 108: ...9 Attachments FISCHER Mess und Regeltechnik GmbH 108 BA_EN_DE90 Fig 141 CE_DE_DE90_ATEX ...
Страница 113: ...FISCHER Mess und Regeltechnik GmbH BA_EN_DE90 113 Notes ...
Страница 114: ...FISCHER Mess und Regeltechnik GmbH 114 BA_EN_DE90 ...
Страница 115: ...FISCHER Mess und Regeltechnik GmbH BA_EN_DE90 115 ...