2 Product and functional description
2.1 Delivery scope
• NK10 according to specification (see order code)
• Operating Manual
• SIL safety manual for version NK10 … U0600
2.2 Use as intended
The NK10 fill level limiter is used in thermo-technical and process plants as a
safeguard against the fill level falling below the lowest permissible level. As a
limiter the device conforms to the requirements of DIN 4754.
The devices in this series are...
• type-tested in compliance with DIN 4754-3
• certified to DNVGL-CG-0339
• Functional safety as per IEC 61508/61511
• certified to directive 2014/68/EU
Copies of the certificates can be found in the appendix to the operating manual.
2.3 Function diagram
1
2
3
6
4
9
8
7
10
approx. 10 mm
approx. 60 mm
5
Fig. 1:
Function diagram
1
Swimmer
2
Swimmer rod
3
Metal bellows
4
Test button
5
Switch lever
6
Micro-switch S1
7
Cable screw connection
8
Flange and counter-flange
9
Welding socket
10
Tank
Содержание NK10 B
Страница 1: ...Operating manual NK10 Fill Level Limiter 09005111 BA_EN_NK10 Rev ST4 E 01 19 09005111 ...
Страница 19: ...FISCHER Mess und Regeltechnik GmbH Attachments 8 BA_EN_NK10 19 28 Fig 13 CE_DE_NK10 part2 ...
Страница 22: ...8 Attachments FISCHER Mess und Regeltechnik GmbH 22 28 BA_EN_NK10 Fig 16 DNVGL_TAA000020S_Page_2 ...
Страница 23: ...FISCHER Mess und Regeltechnik GmbH Attachments 8 BA_EN_NK10 23 28 Fig 17 DNVGL_TAA000020S_Page_3 ...
Страница 27: ...FISCHER Mess und Regeltechnik GmbH Attachments 8 BA_EN_NK10 27 28 Fig 21 SIL_IEC61508_DE_EN 1 Part2 ...