4 | Technical data
FISCHER Mess- und Regeltechnik GmbH
16/24
BA_EN_ME12_ATEX
4.6 Application conditions
Ambient temperature range
-10 °C … +70 °C
Storage temperature range
-20 °C … +85°C
Medium temperature range
-10 °C … +85 °C
ATEX
EN 60079-0:2012 + A11:2013
EN 60079-15:2010
EN 60079-31:2014
EMV
EN 61326-1:2013
EN 61326-2-3:2013
RoHS
EN IEC 63000:2018
Protection type
IP 65 acc. to EN 60529
Materials of the parts that come into contact with the surroundings
Housing
CrNi Steel 1.4305
Device plug screw lid
Polypropylene, black
Device plug
Polyamide, brass, zinc
Cable socket
Polyamide, polycarbonate, brass, zinc
Materials of the parts that come into contact with the measuring medium
Process connection
CrNi Steel 1.4404
Sensor membrane
Ceramic Al
2
O
3
Seal
1)
FKM
Fluorinated rubber, Viton®
CR
Chloroprene rubber, Neopren®
EPDM Ethylene propylene diene rubber
H-NBR Hydrogenated acrylonitrile butadiene rubber
FFPM
Perfluorinated rubber, Kalrez®
1)
see order code
4.7 Parameters
The ME12 pressure transmitter is fully configured on delivery, however it can
also be remotely configured on site. A PC, an interface, which is available as an
accessory and the PC software
transmitter programmer
are required for con-
figuration.
The EU13 with a USB interface is used for pressure transmitters with 2-line con-
nections.
The following parameters can be set
Characteristic curve
Increasing / decreasing
Attenuation
0 … 200 s
Offset correction
±25 %FS
Margin correction
±25 %FS
Signal limits
Current output
(settable)
Upper limit
3.5 … 22.5 mA
Lower limit
3.5 … 22.5 mA
Error signal
3.5 … 22.5 mA