6 | Technical data
FISCHER Mess- und Regeltechnik GmbH
24 / 28
BA_EN_DE43
Pre-set data format
Baud rate
9600 Baud
Parity
None
Stopbit
1
Supported Modbus functions
0x02
Read Discrete Inputs
0x03
Read Holding Registers
0x04
Read Input Registers
0x2B / 0x0E
Read Device Identification
For more information about this, please refer to the operating instructions and
online
http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf
6.4 Auxiliary energy
nominal voltage
24 V DC
Admissible operating voltage 18 … 30 V DC
Absorbed power
Max. 2 W
6.5 Operating conditions
Ambient temperature range
-10 … +70 °C
Storage temperature range
-20 … +70 °C
Medium temperature range
-10 … +70 °C
Protection
IP65
EMC
EN 61326-1:2013
EN 61326-2-3:2013
RoHS
EN 50581:2012
6.6 Construction design
Installation position
User-defined
Max. dimensions (WxHxT)
116 x 103 x 76 mm
Weight
375 g
6.6.1 Connections
Modbus connector 1
M12 round plug connector
(5-pin, male, max. 2A)
Plug 1 for supply and bus signals
Modbus connector 2
M12 round plug connector
(5-pin, female, max. 2A)
Plug 2 for forwarding the signals to the next
BUS participant or to connect a BUS termina-
tion plug
Digital inputs E1 … E4
M8 round plug connector (3-pin, female)
Depending on the model, 0, 2 or 4 proximity
switches can be connected
Process connection option 1
Aluminium CK screw connection for 6/4 or 8/6
mm hose
Process connection option 2
Pneumatic plug connector for 6/4 or 8/6 mm
hose