4 | Start-up
FISCHER Mess- und Regeltechnik GmbH
14 / 28
BA_EN_DE43
Baud rate
S1
S2
S3
S4
S5
S6
S7
S8
1200
OFF
OFF
OFF
X
ON
2400
ON
OFF
OFF
X
ON
4800
ON
ON
OFF
X
ON
9600
OFF
ON
OFF
X
ON
19200
ON
OFF
ON
X
ON
38400
OFF
OFF
ON
X
ON
57600
ON
ON
ON
X
ON
Parity
S1
S2
S3
S4
S5
S6
S7
S8
None
OFF
OFF
X
X
ON
Identical parity
ON
OFF
OFF
X
ON
Not identical parity
OFF
ON
OFF
X
ON
It is not possible to combine identical or non-identical parity with 2 stopbits.
Stopbits
S1
S2
S3
S4
S5
S6
S7
S8
1 stopbit
OFF
X
ON
2 stopbits
ON
X
ON
The device needs to be restarted to confirm the settings. To do this, disconnect
the device briefly from the power supply (plug 1).
4.2.2 Modbus address
To set the Modbus address, the switch S8 must be in the position OFF.
S1
S2
S3
S4
S5
S6
S7
S8
Modbus Address
OFF
Fig. 18:
DIP switches
The address is entered in the dual system. The switches S1 to S7 represent the
respective setting value as follows:.
S1
S2
S3
S4
S5
S6
S7
Binary
2
0
2
1
2
2
2
3
2
4
2
5
2
6
Decimal
1
2
4
8
16
32
64
For example:
The Modbus address 24 should be set.
S1
S2
S3
S4
S5
S6
S7
S8
Switch set-
ting
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
Priority
0*2
0
0*2
1
0*2
2
1*2
3
1*2
4
0*2
5
0*2
6
Total
0
+0
+0
+8
+16
+0
+0
=24
The device needs to be restarted to confirm the settings. To do this, disconnect
the device briefly from the power supply (plug 1).