Warnings and error messages
20.7.15
Kapitel/Chapter 15: Warnings and error messages - Seite/Page 211
15. Warnings and error messages
To enable the safe operation of the generator, the Panda iControl2 controller is programmed with a series of
warnings and error messages that influence the generator operation.
15.1 Warnings
Warnings are issued when the variable being monitored, e.g. temperature, reaches a defined warning threshold.
The warnings are issued on the Panda iControl2 panel display via the cyclical display of the word „HIGH“ or „LOW“,
alternating with the measured value, e.g. the temperature. Warnings do not become active until the time between
reaching the threshold value and the defined delay has expired.
Note:
Warnings do not result in the generator or the controller
being switched off.
15.1.1 Examples of warnings on the display:
Fig. 15.1.1-1: Warning: „Battery power too low“
Warning: „Battery power too low“
Fig. 15.1.1-2: Warning: „Winding temperature too high“
Warning: „Winding temperature too high“
Содержание Panda 25i PMS
Страница 10: ...Seite Page 10 Kapitel Chapter 1 20 7 15 Leere Seite Intentionally blank...
Страница 146: ...Generator Failure Seite Page 146 Kaptitel Chapter 8 Generator Failure 20 7 15...
Страница 158: ...Tables Seite Page 158 Kaptitel Chapter 9 Tables 20 7 15...
Страница 180: ...Inverter Panda PMGi 25 Seite Page 180 Kaptitel Chapter 10 Inverter Panda PMGi 25 20 7 15...
Страница 208: ...Seite Page 208 Kapitel Chapter 13 Installation 20 7 15 Leere Seite Intentionally blank Installation...
Страница 210: ...Seite Page 210 Kapitel Chapter 14 Maintenance 20 7 15 Leere Seite Intentionally blank Maintenance...
Страница 216: ...Seite Page 216 Kapitel Chapter 16 Annex 20 7 15 Leere Seite Intentionally blank Annex...