General operation
Seite/Page 264 - Kaptitel/Chapter H: General operation
19.8.14
H.7.6 Configuration and adjustment
H.7.6.1 Configuration and setting sheet KE05
Standard jumpering for use as Slave-Panel in connection with
two
Master-Slave-Adapters RE0706 and a Generator
Control Panel P6+ RE0703 as Master-Panel. Panel only for 12 V-operation.
The safety device is installed with the value 0,63 AT. The circuit parts for 24 V-operation are not equipped.
Fig. H.7.6-1: Settings of soldered jumper for this configuration (column Conf.)
The solder jumpers are marked on the printed circuit board (with jumper no. and at three-part solder jumper with soldering surface no.)
X
= Jumper must be so set
XM
= Jumper, function must be so set on the master panel is selected
M
= Jumper must be set exactly the same, as on the master panel,
(1): Equivalent resistance for load control lamp e.g. for use with three-phase alternator also integrated automatic controller of Bosch. The resistance value is 68
Ω
3 W,
i.e. only for 12 V.
(2): A closed contact switches the appropriate input to GND.
Jumper
Status
Conf.
Description
J1
closed
during operation of the start button heat is along-operated
open XM
Function
deactivated
J3
1-2
Dynamo excitation resistor 68R is switched on with Fuel-Pump (1)
2-3
Dynamo excitation resistor 68R is switched on with Panel-ON (1)
open
XM
Dynamo excitation resistor is deactivated
J101
closed
M
12 V - operation
open
M
24 V - operation (not possible)
J201
1-2
T-Engine-input, for contact, which opens in case of error (2)
2-3
XM
T-Engine-input, for contact, which closes in case of error (2)
J202
1-2
Water leak-input / Replace air filter, for contact, which opens in case of error (2)
2-3
XM
Water leak-input / Replace air filter, for contact, which closes in case of error (2)
J203 1-2
Oil-Press-input,
for contact, which opens in case of error (2)
2-3 XM
Oil-Press-input,
for contact, which closes in case of error (2)
J204
1-2
AC-Fault-input / Fuel level, for contact, which opens in case of error (2)
2-3
XM
AC-Fault-input / Fuel level, for contact, which closes in case of error (2)
J205
1-2
T-Winding-input, for contact, which opens in case of error (2)
2-3
XM
T-Winding-input, for contact, which closes in case of error (2)
J206
1-2
M
Input Water leak has red LED and switches off
2-3
M
Input Water leak has yellow LED and does not switch off
J207
1-2
M
Input AC-Fault has red LED and switches off
2-3
M
Input AC-Fault has yellow LED and does not switch off
J208
1-2
M
DC-Control-Signal (-) = OK dynamo 12 V at Kubota Z 482 / D 722 engines
2-3
M
DC-Control-Signal (+) = OK three-phase DC-alternator
J209
1-2
M
DC-Control-Signal (-) = OK dynamo 12 V at Kubota Z 482 / D 722 engines
2-3
M
DC-Control-Signal (+) = OK three-phase DC-alternator
J210
closed
Input AC-Fault has Pull-Up-current
10 mA
open
XM
Input AC-Fault has Pull-Up-current
2,5 mA
Содержание Panda 10000
Страница 110: ...Installationshinweise Seite Page 110 Kaptitel Chapter B Installationshinweise 19 8 14 Fig B 18 0 2 L ftersteuerung 230V...
Страница 230: ...Seite Page 230 Kapitel Chapter E St rungen am Generator 19 8 14 Leere Seite Intentionally blank St rungen am Generator...
Страница 242: ...Tabellenteil Seite Page 242 Kaptitel Chapter F Tabellenteil 19 8 14...
Страница 266: ...Seite Page 266 Kapitel Chapter H General operation 19 8 14 Leere Seite Intentionally blank General operation...
Страница 268: ...Seite Page 268 Kapitel Chapter I Measurements 19 8 14 Leere Seite Intentionally blank Measurements...