Installation Instructions
AGT 6000 PVMV-N 12V_24V - Chapter B: Installation Instructions
Page 47
All electrical safety installations have to be made on board.
Electrical fuses
It is absolutely essential that the electrical system installation is inspected by a qualified electrical
technician. The generator should have its own AC input electrical fuses. The fuses should be
sized such that the rated current of the generator on each of the individual phases is not excee-
ded by more than 25%.
Data for gensets with power output greater than 30kW on request!
The fuses must be of the slow type. A 3-way motor protection switch must be installed to protect
the electrical motor.
Required cable cross-sections
The following recommended electrical cable dimensions (cross sections) are the minimum requi-
red sizes for a safe installation. (see Table 3, “Cable cross section,” on page I)
B.3 Connection to Starter Battery-Block
An own separate starter battery must be installed for the generator.
The positive cable (+) of the battery is attached directly at the solenoid switch of the starter motor
(position 1). The negative cable (-) of the battery is attached underneath the starter motor at the
engine mount (position 2).
ATTENTION!
It must be guaranteed that first the cables are attached at the generator and then at the
battery. To avoid large voltage drops the battery should be installed as near as possible to
the generator. The positive terminal of the battery is attached at the red cable, the negative
pole at the blue cable.
ATTENTION!
The positive cable of the starter battery and of the battery bank must be secured with a
battery main switch and a siutable fuse
B.4 Remote control Panel - see remote control panel datasheet
If there is an automatic starting requirement and if the remote control panel is switched off, then
this automatic starting requirement is ignored. Automatic starting is only possible if after switching
on of the remote control panel the automatic starting requirement takes place.
B.4.1 Electronic starter control unit
If there is an automatic starting requirement and if the remote control panel is switched off, then
this automatic starting requirement is ignored. Automatic starting is only possible if after switching
on of the remote control panel the automatic starting requirement takes place.
Содержание AGT 6000 PVMV-N
Страница 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Страница 6: ......
Страница 10: ...8 Socket wrench set Hexagon wrench keys ...
Страница 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Страница 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Страница 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Страница 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...