5.7.2 The Electrical Fuel Pump
Fig. 5.7.2-1: Electrical Fuel Pump
Electrical fuel pump
With the Panda generator is usually supplied an external,
electrical fuel pump (DC). The fuel pump must be installed
close at the fuel tank. The electrical connections are pre-
loaded at the generator with the lead planned.
Suction hight of the pump: max. 1,2 m at 02, bar
Diameter of fuel lines: section 8.10, “Diameter of conduits,”
on page 177.
5.7.3 Connection of the fuel lines at the tank
Lead the return fuel pipe connected to the day tank to the floor
The return pipe connected to the tank must be dropped to the same depth as the suction pipe, if the generator is
mounted higher than the tank, in order to prevent fuel running back into the tank after the motor has been switched
off, which can lead to enormous problems, if the generator is switched off for a long period.
Non-return valve in the suction pipe
A non-return valve must be fitted to the suction pipe, which prevents the fuel flowing back after the generator has
been switched off, if it is not possible to use the return flow pipe as a submerge pipe placed in the tank. The instruc-
tions "Bleeding Air from the Fuel System" must be read after initial operation or after it has stood still for a long
period, in order to preserve the starter battery.
ATTENTION!
Non-return valve for the fuel return pipe
If the fuel tank should be installed over the level of the genera-
tor (e.g. daily tank), then a non-return valve must be installed
into the fuel return pipe to guarantee that through the return
pipe no fuel is led into the injection pump.