Installation Instructions
30.10.12
Kapitel/Chapter 6: Installation Instructions Seite/Page 77
6.8.8 Pay attention to the following item at the horizontal assembly of the radiator:
To avoid damages of the fan motor please bore some holes on the backside of the fan (diameter approx 4mm).
Because water can enter the fan (rainwater, condenswater, sweatwater etc.). The water can run out through these
holes. (see below 02) Generally a fan is a wearing part and should be changed one time a year.
Fig. 6.8.8-1: Preperation of the fan
6.8.9 Distance from the radiator to the unit
The coolant water pump mounted on the generator is so laid out that a
maximum
distance of up to 5 mtrs length
from the radiator is possible. The hose cross-section must be laid out accordingly. The minimal internal diameter
amounts to 18mm (Panda 4500). A hose must be used for both sides (forward and back flow) which is resilient to
pressure and high temperatures (at least 120°C).
6.8.10 Coolant expansion tank
It is absolutely essential, that a expansion tank, that can be aerated, is fitted adjacent to the radiator. The ventilation
pipe should, if possible, be fitted to the radiator’s highest position. For this, a pipe with a maximum diameter of
10mm suffices, which must be fed to the expansion tank. A further pipe, which must be fitted to the floor of the
expansion tank, can be fitted to the cooling system in any desired place (i.e. T-piece). Frequently a connection is
provided on the radiator itself. The coolant expansion tank is not normally supplied by Fischer Panda. For this a
standard vehicle expansion tank is the most suitable. Vehicle accessory range is the most suitable.
6.8.11 Antifreeze
The
antifreeze
concentration must be regularly checked in the interests of safety. The antifreeze solution supplied
from the factory provides protection to -15°C. If lower temperatures are occasioned during transportation or storage,
then the coolant must be drained. The cooling system is, however, so arranged that the draining of the coolant is
only possible in the assembled state, when air under pressure is blown into the system. Air pressure of approx. 0.5b
suffices, in order to blow out the water.
2
1
1. Plug for fan control
2. Bores (diameter 4mm)
Содержание 5000i PVK-U
Страница 36: ...Seite Page 36 Panda_5000i_PVMV N_Book_eng R02 30 10 12 Leere Seite Intentionally blank Basics...
Страница 48: ...The Panda Generator Seite Page 48 Kaptitel Chapter 4 The Panda Generator 30 10 12...
Страница 126: ...Generator Tables Seite Page 126 Kaptitel Chapter 8 Generator Tables 30 10 12...
Страница 146: ...Installation Page 146 Chapter 11 Installation 30 10 12 11 3 Dimensions Fig 11 3 0 1 Housing of the Panda iControl2 panel...
Страница 150: ...Page 150 Chapter 11 Installation 30 10 12 Intentionally left blank Installation...
Страница 152: ...Page 152 Chapter 12 Maintenance 30 10 12 Intentionally left blank Maintenance...
Страница 158: ...Page 158 Chapter 14 Annex 30 10 12 Intentionally left blank Annex...