Generator Failure
26.1.11
Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 7: Generator Failure Seite/Page 115
7.5.1 Discharge the capacitors
Fig. 7.5.1-1: Capacitors
1) Switch off generator
2) Disconnect starter battery
3) Generator power terminal box
4) Remove the caps
The capacitor is discharged, by short circuit the two contacts.
In addition use the cone end of an isolated screwdriver.
Sample picture 4000s FC
7.5.2 Check and discharge the capacitors
ATTENTION!
Before working (installation) on the System read the section
“Safety Precautions” auf Seite 6 in this Manual.
Attention!:
NEVER check the capacitors whilst the generator motor is run-
ning! Charged capacitors can be lethal. Do not contact the
capacitors with bare fingers or non-insulated metallic objects!
In order to test the capacitors, the terminal lead wires have to
be disconnected using pliers or a screwdriver with insulated
handle(s). Once the wires have been removed, the capacitors
must be discharged by bridging the capacitor terminals with a
discharge reactor.
The capacitors can be checked using a multimeter with capacitor measuring.
The capacitors fitted inside the cabinet are discharged over the soldered resistor at every capacitor. The discharge
over the discharge reactor (see special tools) is security because the capacitor voltage is lethal.
Содержание 4000s PMS FC
Страница 24: ...Seite Page 22 General R01 1 26 1 11 Leere Seite Intentionally blank General References and Regulations...
Страница 68: ...Seite Page 66 Panda_4000s_PMS_SCB_FCB_eng R04 26 1 11 Leere Seite Intentionally blank The Panda Generator...
Страница 112: ...Seite Page 110 Panda_4000s_PMS_SCB_FCB_eng R04 26 1 11 Leere Seite Intentionally blank Maintenance Instructions...
Страница 122: ...Seite Page 120 Panda_4000s_PMS_SCB_FCB_eng R04 26 1 11 Leere Seite Intentionally blank Generator Failure...