Generator control system
Based on VCS183
DS_VCS183
Page 33
Rev. 06
www.fischerpanda.com
©Fischer Panda generators Inc.
faults and some messages are suppressed. If more than on fault/message is active then all active
messages/faults will cycle through the display at a rate of approx. 0.7sec.
The panel will only show readings that are currently enabled:
•
If the control system was configured for 120V AC output only then one output voltage and one
output current will be shown
•
If it was configured for 120/240V then a total of 3 output voltages (L1-N, L2-N and L1-L2) and 2
output currents (I1, sensed on L1 and I2 sensed on L2) will be shown.
•
If any temperature sensor or the oil pressure sensor is disabled then it will not be shown at all.
•
Readings that are currently not available (as is the case with sensors that are enabled but
missing) or that do not make sense in actual operational mode (as is the case with power factor
while the generator is not producing electric energy) are shown as “
---
“.
Acoustic alarm
The control panel has an acoustic alarm that may be enabled individually on each panel. If it is enabled it
will be triggered if one or more major faults are active. The user may acknowledge (and mute) this
acoustic alarm by clicking button S2. By doing so all actually active major faults are acknowledged
throughout all panel pages (i.e. flipping display pages will not re-trigger the beeper). If a major fault
becomes inactive and then active again the panel beeper gets re-triggered.
Starting and stopping the generator
The generator may be started (if no major faults are pending) and stopped from within any one of the
basic display pages in one of several ways:
1.
By clicking button S5
2.
By sending the appropriate command via NMEA 2000 network
3.
By toggling remote start
–
if remote start was configured for dynamic operation (
4.
Via remote start stop input.
Starting methods 1..3 have same priority meaning the generator may be started with one method and
may be stopped with another one without any restrictions. Method 4 has same priority as methods 1
…3
if the control system was configured to operate with dynamic inputs; behaving is different though if it
was configured for static inputs. Details about static / dynamic inputs and potential conflicts are covered
in more detail under paragraph