7.
Using compressed air to clean the tip, blow out the gas lines, both forward and backward.
8.
Inspect and clean the primary orifice located upstream of the removable fixed orifice.
9.
Replace the removable orifice in its original location.
High Energy Igniter
Remove and inspect the spark rod assembly every 6 months or during planned boiler outage, per the
HEI Service Manual.
Combustion Air Fan and Motor Set
Every 6 months, ensure that igniter is receiving adequate air flow.
STORAGE
Store the SureFire™ igniter in a clean, dry atmosphere. When possible, store the assembly in its orig-
inal shipping container until used. If the SureFire™ igniter is removed from its shipping container,
store it in a horizontal position supported at both ends of the guide tube. Protect both guide tube ends
from damage due to inadvertent bumps or blows. Cover the SureFire™ igniter with plastic to keep it
free of dust and dirt. Storage longer than 30 days requires humidity less than 85% and temperature
less than 120°F.
FIGURE 6.
SureFire Model 20 Gas Igniter Output Curve