DESCRIPTION

The MBCE-110/230FR modules provide visual indication and electrical outputs that
signal the user regarding flame presence in a combustion chamber. The module uses
Fireye flame rods to sense flame presence independently or as components in a
burner management system. Many operational characteristics are provided including:

 

CE approved 

 

Self-contained: 110 VAC, 50/60 Hz: MBCE-110FR-1, MBCE-110FR-3

230 VAC, 50/60 Hz: MBCE-230FR-1, MBCE-230FR-3

 

Flame Rod compatible

 

Flame ON/OFF LED indicator

 

4-20mA permits direct reading of flame signal strength

 

Uses CE approved 11-pin relay base 

 

Panel surface or DIN-rail mounting 

 

Self-check

The unit provides a cost effective, self-checking method of monitoring flames using

the ionization principle.

Check with Fireye for more details by contacting your local distributor or by check-
ing the Fireye home page at www.fireye.com.

NOTE: 

When the MBCE-110/230FR modules are used, additional means must be furnished to provide

those functions usually provided by flame safeguard control systems to meet local regulations (i.e.:
safe start check, valve closure, starting and running interlocks, safety timings, etc.).

WARNING: The Equipment described in this manual is capable of causing property damage,
severe injury, or death. It is the responsibility of the owner or operator to ensure that the equip-
ment described is installed, operated and commissioned in compliance with the requirements of
all national and local legislation, which may prevail. Installation, commissioning, or adjustment
of this product MUST be carried out by suitably trained engineer or personnel qualified by
training or experience.

NOTICE: When Fireye products are combined with equipment manufactured by others and/
or integrated into systems designed or manufactured by others, the Fireye warranty, as stated
in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any
other equipment or to the combined system or its overall performance.

MBCE-110/230FR

Flame Sensor

Module

MBCE-1001

FEBRAURY 6, 2017

FMEDA

SIL2

SEE NOTE 1 ON PAGE 4

exida

Содержание MBCE-110FR

Страница 1: ...ust be furnished to provide those functions usually provided by flame safeguard control systems to meet local regulations i e safe start check valve closure starting and running interlocks safety timi...

Страница 2: ...001 MBCE 110FR 3 Single channel module 110 VAC 50 60 Hz use with flame rod 3 sec FFRT MBCE 1001 MBCE 230FR 1 Single channel module 230 VAC 50 60 Hz use with flame rod 1 sec FFRT MBCE 1001 MBCE 230FR 3...

Страница 3: ...inal 4 S2 Terminal 8 local panel ground Power Terminals 4 and 8 240 360 VAC Note Measured with digital VOM Terminals 5 and 8 are internally connected Sensitivity Flame Rod 3 A 100 Meg ohms IP Rating I...

Страница 4: ...FIR 09 10 26 R001 dated December 13 2010 Fireye certifies that the MBCE Flame Sensor Modules are suitable for installations up to and including SIL2 Example of product label FIGURE 2 DIMENSIONS OF DIN...

Страница 5: ...g dis tance the shield should not be grounded keep in mind that an underground shield provides less pro tection against electrical interference Depending on field connections sensor wiring can be up t...

Страница 6: ...T TERMINAL NO TERMINAL NAME DESCRIPTION DIRECTION RATING 1 11 OPEN UNUSED N A 2 A1 4 20mA COM 4 20mA COMMON LOCAL GROUND 3 14 4 20mA OUT 4 20mA OUTPUT OUTPUT 28 VDC 20mA max 4 12 S1 FLAME ROD EXCITATI...

Страница 7: ...forms of ground connection Likewise 4 20mA COM is the return path at the wiring base and MUST NOT be attached or referenced to earth ground or other forms of ground connection FIGURE 3 TYPICAL APPLICA...

Страница 8: ...und defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREY...