6.2
Programming Module Version 3
When using a discharge delay module, the FP-08450/08451 Fire Control Panel
must be programmed for extended discharge.
(See FP-08450 or FP-08451 Manual)
The Delay Timer Switch allows for the activation of the
connected FirePro generators to be delayed for a period
of up to 255 seconds after the FIP has entered an alarm
condition. Individual programming of modules
must
not
exceed 4.5 minutes (the total time power is applied
to the activation circuit).
Each switch on the Delay Timer has a separate delay
value (in seconds) as follows:
The delay time is programmed by setting the required switches
to the “OFF” position.
When multiple switches are used, the
delay values are added together, allowing for any delay time
between 1 to 255 seconds to be programmed.
Example of common delay times can be programmed as follows:
Note:
The settings of the module should be recorded in the service logbook and marked in
the space provided on the front of the module.
Delay Timer Switch
Switch Number
1
2
3
4
5
6
7
8
Delay Value
1 sec
2 sec
4 sec
8 sec
16 sec
32 sec
64 sec
128 sec
Delay Time
Switch Positions
Delay Time
Switch Positions
2 seconds
60 seconds
15 seconds
90 seconds
20 seconds
120 seconds
30 seconds
240 seconds