3.3
How to install a Discharge Delay Module
Connecting ADDITIONAL UNITS
USING for DELAYED DISCHARGE
This shows 3 x FirePro Generators operating
immediately (through the Normal Activation Circuit)
and 1 FirePro unit firing after a delay.
This shows 2 x Firepro Generators operating ONLY
AFTER DELAY.
The 3k3Ω E
OL resistor must be in
place on the Normal output of a fault will display
3.4
Maximum FirePro units that may be connected
12v DC
2 units per output
24v DC
4 units per output
3.5
Maximum Number of Discharge Delay Modules that can be used
Maximum of 10 Modules may be used on any single panel
–
from an electrical point of view.
Actual maximum will be determined by delay programming. If more modules are required,
consult with your supplier.