660/860 SERIES OPTICAL 

FLAME DETECTORS

Installation and operating  

service manual

DMLieferant     

Тел

.: +7 (499) 990-05-50; +7 (800) 775-29-59     dmliefer.ru

Содержание Omniguard 660 Series

Страница 1: ...660 860 SERIES OPTICAL FLAME DETECTORS Installation and operating service manual DMLieferant 7 499 990 05 50 7 800 775 29 59 dmliefer ru...

Страница 2: ...tricity from an ungrounded source including the human body may damage the electronic circuitry of the Omniguard Series 660 and 860 Flame Detectors Use one or more of the following methods when handlin...

Страница 3: ...output Relay contacts rated at 2 Amps 30 VDC Resistive Operating Temperature 40 F to 185 F 40 C to 85 C Storage Temperature 85 F to 212 F 65 C to 100 C Standard Features High Temp Model Relay contact...

Страница 4: ...oexistence of UV and IR radiation but also their presence in specific ratios The ratio must conform to the radiation pattern of specific fires see Figure 3 This patented Fire Event Analysis FEA ensure...

Страница 5: ...ended for smoldering or electrical fire hazards The following is a partial list of fuels which emit ultraviolet and infrared radiation Response time and detection distances vary Consult Firefly AB app...

Страница 6: ...so that it will view the base of the area to be protected 5 Complete the installation by wiring the detector according to the wiring diagram located inside the rear cover Before assembling the detect...

Страница 7: ...8 Program 9 Option Off On No Program 9 Denotes factory settings for auto test units only Fig 9 switch configurations for the 660 0xxxx UV Flame detector SPST dip switch S1 located on board p n 71044...

Страница 8: ...fails manual test will open when SW7 is on and no loop is present Note The amber LED will be illuminated when relay opens unless there is a loss of power Note Any adjustments to the user options liste...

Страница 9: ...acket formation is comprised of the byte definition shown in Table 4 The first byte is the protocol start value for the control packet The second byte represents the detector address high byte which i...

Страница 10: ...test A detector that fails auto test due to dirty optical surfaces may be capable of detecting fire but its effectiveness will be limited from 50 to 70 obscuration Cleaning Procedure Locate the follo...

Страница 11: ...or 11 Look for loose or intermittent connections During normal operation the fault outputs will change state on power up The output will return to its original state if power to the detector is remove...

Страница 12: ...workmanship or materials This warranty shall be valid only if the product is returned within the applicable warranty period to the factory at Stockholm Sweden properly packed and with all transportati...

Страница 13: ...0 Latching 1 Non Latching Designation Ultraviolet flame detector To order Model 660 please specify Fire type 0 Hydrocarbon 1 Hydrocarbon Non hydrocarbon Housing material conduit entry 0 Aluminium 3 4...

Страница 14: ...14 Firefly AB Oktober 2016 Notes DMLieferant 7 499 990 05 50 7 800 775 29 59 dmliefer ru...

Страница 15: ...15 Firefly AB Oktober 2016 DMLieferant 7 499 990 05 50 7 800 775 29 59 dmliefer ru...

Страница 16: ...8 449 25 00 Fax 46 0 8 449 25 01 E mail omniguardsales firefly se www omniguardbyfirefly se Address Heliosgatan 3 120 30 Stockholm Sweden Publication No 1031229 Rev M DMLieferant 7 499 990 05 50 7 800...