FireClass Fire detection system
XLM800
Fixing instructions Doc. version 1
1/4
FireClass XLM800 Loop Expansion Module
Installation
Introduction
The XLM800 fits piggy-back onto the FIM or exist-
ing XLM800 and is used as follows:
To provide a 3rd and 4th loop in a 4 loop Fire-
Class controller.
The XLM configuration is as follows:
Features
The FireClass XLM800 Loop Expansion Module
controls the communications between the detec-
tors (and other ancillaries) connected on the 2-wire
loop circuits and the controller. In addition, the
XLM800 contains line isolation circuits which pro-
tect the loop driver circuit from short-circuit condi-
tions.
Technical Specification
Table 2 shows the technical specification for the
XLM800 loop expansion module.
XLM Arrangement Configuration
1 x XLM
Base Link
(JP3 fitted (see item 9
in Fig. 2) ),
FIM loops (A&B)
XLM loops (C&D)
Table 1: XLM Configuration
Parameter
Value
System Compatibility
Use only with FireClass
Fire Controllers
Table 2: Technical Specifications
Environment
Indoor Application only
Operating
Temperature of panel
-5 to +40
o
C
Storage Temperature
-20 to +85
o
C
Operating Humidity
Up to 95% non-
condensing
Dimensions (HWD)
17.5 x104 x196 mm
Electrical
Characteristics
Input Voltages:
+5V +/-0.25 V
+24V +/-2.4 V
+40V +/-2 V
Battery Requirements
Refer to the latest ver-
sion of FireClass
Designer for Battery
and Alarm Power
Supply Calculation
Electromagnetic
Compatibility
Product family
standard EN50130-4
in respect of
Conducted
Disturbances, Radiated
Immunity, Electrostatic
Discharge, Fast
Transients and Slow
High Energy.
EN50081-1 for
emissions.
Parameter
Value
Table 2: Technical Specifications (cont.)