FireClass Fire detection system

XLM800

Fixing instructions  Doc. version 1

1/4

FireClass XLM800 Loop Expansion Module 
Installation

Introduction

The XLM800 fits piggy-back onto the FIM or exist-
ing XLM800 and is used as follows:

To provide a 3rd and 4th loop in a 4 loop Fire-
Class controller.

The XLM configuration is as follows:

Features

The FireClass XLM800 Loop Expansion Module 
controls the communications between the detec-
tors (and other ancillaries) connected on the 2-wire 
loop circuits and the controller. In addition, the 
XLM800 contains line isolation circuits which pro-
tect the loop driver circuit from short-circuit condi-
tions.

Technical Specification

Table 2 shows the technical specification for the 
XLM800 loop expansion module.

XLM Arrangement Configuration

1 x XLM

Base Link 

(JP3 fitted (see item 9 
in Fig. 2) ),
FIM loops (A&B)
XLM loops (C&D)

Table 1: XLM Configuration 

Parameter

Value

System Compatibility

Use only with FireClass 
Fire Controllers

Table 2: Technical Specifications 

Environment

Indoor Application only

Operating 
Temperature of panel

-5 to +40

o

C

Storage Temperature

-20 to +85 

o

C

Operating Humidity

Up to 95% non-
condensing

Dimensions (HWD)

17.5  x104  x196 mm

Electrical 
Characteristics

Input Voltages: 
+5V +/-0.25 V
+24V +/-2.4 V
+40V +/-2 V

Battery Requirements

Refer to the latest ver-
sion of FireClass 
Designer for Battery 
and Alarm Power 
Supply Calculation

Electromagnetic 
Compatibility

Product family 
standard EN50130-4 
in respect of 
Conducted 
Disturbances, Radiated 
Immunity, Electrostatic 
Discharge, Fast 
Transients and Slow 
High Energy.
EN50081-1 for 
emissions.

Parameter

Value

Table 2: Technical Specifications (cont.)