FIRECLASS Prescient III
4 Panel Operation
Application, Installation & Commissioning Doc. version 2
27
4
Panel Operation
4.1
Circuit Configuration
Options
4.2
Circuit Select Cursor
The Circuit Select Cursor is a rapidly flashing fault/disa-
blement LED for the selected circuit. The cursor flashes
rapidly for 0.5 seconds then switches off for 1 second.
During the OFF period, the LED will display the current
status for the selected circuit (i.e. OFF if circuit is nor-
mal, ON if in Test or Disabled, pulsing if the circuit is in
fault).
4.2.1
Disable, Re-enable, Test
To disable/re-enable or test any of the circuits in Table
1, the required circuit is selected by moving the Circuit
Select Cursor and then pressing
INSCHAKELEN
,
UITSCHAKELEN
or
TEST
as required. The process is as
follows:
1
Press the
SELECTEER AAN/UIT
button. The Select
Cursor will appear on the
DOORMELDING BRAND
fault LED.
Circuit
Disabled
Test Mode
Intrinsically
Safe
Zone 1
a
Zone 2
Auxiliary
Zone
Field
Manual
Release
Group
Operation
N/A
Panel
Manual
Release
N/A
N/A
Sounder 1
Group
Operation
Group
Operation
Sounder 2
Extinguishing
Sounder
Group
Operation
Actuator 1
N/A
Actuator 2
N/A
Fire Signal
N/A
N/A
Fault Signal
N/A
N/A
Gas
Released
Signal
N/A
N/A
Shutdown 1
Group
Operation
N/A
N/A
Shutdown 2
N/A
N/A
Shutdown 3
N/A
N/A
Table 5: Circuit Modes
a – Zones 1 & 2 are placed into Test mode together but are cleared individually (safety feature)
N/A-Not Available
-Feature Available without Additional Configuration