remote siting of the FIRERAY 50 an optional BTM800
terminal module can be used with 4 core cable.
The FIRERAY 50 transmitter and receiver units are
mounted in the same housing.
The FC410BDM loop powered beam detector
interface module is contained on a double sided
printed circuit board (PCB) which is fitted into
a custom built fascia plate with a protective
cover being fitted over the PCB, leaving only the
connection terminals exposed. The fascia plate is
then fitted onto a standard dual-gang back box with
BESA fittings.
FC400CH Addressable carbon
mo heat detector
The FC400CH carbon monoxide plus heat detector
forms part of the FC400 series addressable fire
detectors.
The detector is intended to plug into the following
bases:
•
5B 5” universal base
•
FC450IB 5” isolator base
•
FC430SB low power sounder base
•
FC430LPSB loop powered addressable
sounder base
•
FC430LPASB loop powered addressable
sounder beacon base
The detector is designed to transmit digital
signals to a remote FireClass controller, which
represent the status of the carbon monoxide and
the heat elements of the detector. Software within
the controller is used to interpret the returned
carbon monoxide and heat values to raise alarm
or other appropriate response according to the
type of detector configured in the FireClass FC500
(FC501_FC503_FC506) Console.
801RIL Remote LED Indicator
The 801RIL remote indicator is used where a
detector LED is not visible. For example, when the
detector is mounted in a roof void or lift shaft. The
801RIL is mounted to a single gang electrical box
and is supplied with 2 x M3.5 screws.
801HL Remote LED indicator
The 801HL remote indicator is used where a
detector LED is not visible. For example, when the
detector is mounted in a roof void or lift shaft.
The 801HL provides a larger indicator for use in
place of the 801RIL when longer distances are
involved or in VdS influenced markets.
The 801HL can be mounted to any suitable flat
surface and has fixing centres at 60 mm and 80 mm.
HVR800 High voltage relay
The HVR800 high voltage relay interface is a non-
addressable multi-voltage relay module (operating
from 24 VDC, 24 VAC, 120 VAC, and 240 VAC). The
encapsulated HVR800 provides a 10 amp volt-free
contact that can be used to extend the contact
ratings of FC410RIM Addressable Relay Module
applications.
If all HVR800s are powered by 120 VAC or 240 VAC,
a maximum of four HVR800s can be individually
driven and controlled by an FC410MIO small
addressable multi-input and output module. For
AC operation, no external DC power supply unit is
required to operate the relay. When used to switch
24 VDC, the HVR800 must be provided with an
external 24 VDC supply which should be switched
through the clean relay contacts of an FC410MIO or
FC410RIM.
DPK4 and DPK4I
The DPK4 and DPK4I duct probe units have been
developed to detect smoke in ventilation ducts.
These duct probe units can used in combination
with a wide range of detectors and are suitable
for addressable and conventional systems. The
duct probes can operate across a wide range of
air velocities from 1 m/s to 20 m/s. The duct probe
units have a built-in FireClass universal base 5B.
There is a range of aluminium probe tubes available
for air ducts up to 1500 mm.
FIRERAY 50/100-Optical Beam
Smoke Detector
The detector comprises of a transmitter and
receiver contained within one enclosure.
The transmitter emits an infrared light beam that is
reflected through a prism mounted directly opposite
and with a clear line of sight. The reflected infrared
light is detected by the receiver and analysed.
The detector has a maximum lateral detection
defined by the local national standard. As a guide,
a common lateral distance of 7.5 m will be used in
this guide. Use the latest beam detector standards
EN54 part 12, VdS2095 or BS5839 part 1 for further
guidance.