Quick start-up procedure
This procedure allows for the quick start-up of the
FC503 and FC506 fire detection system.
When the loops are wired, electrically verified, and
all the devices have been installed in to the loop, it is
possible to connect the loops terminals to the panel.
Note:
Before powering on the fire control
panel, connect the Earth Line.
By default the setting of switch 45 is set to mains
voltage 230 V.
Procedure
About this task:
1. Turn on the panel and start the FW procedure
to verify or program information for the user
interface and the panel. This information
includes:
- language selection
- panel identification number
- panel type (
FC503
or
FC506
)
- installed batteries capacity (17 Ah or 38
Ah)
2. When the data has been verified or
programmed, enter the date and time. This
ensures consistency of the log file. The panel
starts the first system initialization verifying
the loops integrity.
Note:
The panel in this phase is
configured to manage closed loops (4
wires loop). If it is connected to a spur
(2 wire loop), it generates broken loop
faults.
3. At the end of this first initialization
phase, the user interface displays on
the MAIN screen with the capability
to accept the command and control
functions.
4. Select the function Program by pressing the
1
key.
5. Insert the Installer password. The default
Installer password is 00000.
Note:
Every digit is masked by an
asterisk.
6. Choose an option by pressing the
1
key. The
enrolling procedure starts.
This procedure is divided into three main phases:
1. Auto-learning
2. Auto-addressing
3. Device Mapping
It is possible to stop the
AUTO
option at the end of
each phase; the results are different.
1 Auto-learning
Result
In the auto-learning phase, the panel looks for all
the devices on the loop already addressed with the
service tool.
During this phase, enter what pattern of automatic
assignment of zones to be applied to found
devices (see Figure 26,1B) and enter the sounder's
triggering scheme (see Figure 26, 1A).
If the panel is already configured, any differences
are indicated and you need to decide on how to
proceed. See Figure 26, 1A. In this case, the scheme
of Automatic assignment of the zones
is applied only
to any new devices found.
If you stop the AUTO option at the end of the first
phase the following results occur:
•
The FC503 control panel takes over all devices
with an address between 1 and 250.
•
The FC506 control panel 1
st
loop takes over all
devices with an address between 1 and 250
and the 2
nd
loop takes over all devices with an
address between 1 and 250.
•
The programming device at their default
configuration.
•
Automatic assignment of labels.
•
Automatic assignment of the zones according
to the scheme chosen during that phase.
•
The output channels of the modules enable
to activate on fire alarm of the assigned
zone. The sounders, sounders and beacons,
sounder bases, AV (Audio Visual) bases, and
the FC430SNM modules activate according to
the trigger scheme chosen in in this phase.
If you choose to assign all devices to system
(no zone auto assignment), all of the output
modules, sounders and beacons are triggered
by the Panel alarm condition.
•
The faults NOT PROGRAMMING DEVICE and
wrong addresses are generated in the case of
not addressed devices or with address greater
than 250, respectively.
FC503 and FC506 Addressable Fire Control Panels
66