Doc. # 51583    Rev. B   05/07/01   ECN 01-131

This Supplement has been created to inform installers about the new Signal Line Circuit (SLC) capacity
of 159 detectors and 159 modules per SLC loop; and
Introduce two new FACP software features which (1) provide a synchronized strobe programming
option, (2) allow the control panel to monitor and printout the sensitivity and drift compensation for
each addressable smoke detector connected to the system; as well as to
Provide information concerning 'Positive Alarm Sequence' and 'Printer Supervision'.

I. Synchronized Strobes

NAC Option for Synchronization

Synchronization is a panel feature that controls the activation of notification appliances in such a way that all devices will turn on
and off at exactly the same time.  This is particularly critical when activating strobes which must be synchronized to conform
with a variety of regulations as well as to avoid random activation which could cause a hazardous condition.  The FACP can be
programmed to operate with a variety of manufacturer's devices.

Important:

 When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and

the synchronization feature is selected, only the audible devices will be turned off if the Silence key is pressed.  The visual
devices (strobes, etc.) will continue to operate.

Program Selection for Synchronized Strobes

1. Press the 

Enter 

or 

Mode 

key to display the following LCD readout:

2. Press 

to display the following:

3. Enter the Master level password (default is 

00000

) to display the following:

4. Press 

down arrow

 key once to display the following:

Supplement to MS-9600 Manual, Rev A

Smoke Detector Capacity

Detector Sensitivity & Synchronized Strobes

Positive Alarm Sequence & Printer Supervision

Document 51583   Rev B  05/07/01  ECN 01-131

1=READ@STATUS
2=PROGRAMMING

PROGRAMMING
ENTER PASSWORD
*****

@@@@@PROGRAMMING
1=POINT@PROGRAM

2=ZONE@SETUP
3=LOOP@SETUP

@@@@PROGRAMMING
1=SYSTEM@SETUP

2=AUTOPROGRAM

3=VERIFY@LOOP

Содержание MS-9600

Страница 1: ...tions as well as to avoid random activation which could cause a hazardous condition The FACP can be programmed to operate with a variety of manufacturer s devices Important When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the synchronization feature is selected only the audible devices will be turned off if the Silence key is pressed ...

Страница 2: ...EABLE NAC TYPE 1 BELL 2 HORN 3 STROBE NAC TYPE 1 SYNCED STROBE 2 AUDIBLE 3 SIREN CIRCUIT 11 Press 1 to program the NAC as a synchronized strobe circuit The display will return to the following 12 Press the down arrow key three time to display the following 13 Press 1 to display the following 14 Select the type of synchronized circuit according to the manufacturer s devices installed on the NAC by ...

Страница 3: ...rol panel keypad will display the following LCD screen 2 Press 1 to display the following 3 Press down arrow key four times to display the following 4 Press 3 to display the following 5 Press 3 to print the detector sensitivity data for all addressable smoke detectors installed on the system Refer to the sample printout on the following page for information on interpreting the data Note If a print...

Страница 4: ...amber Drift compensation performs the following functions Allows a smoke detector to retain its original ability to detect actual smoke and resist false alarms even as dirt and dust accumulate Reduces maintenance requirements by allowing the control panel to automatically perform the periodic sensitivity measurements required by NFPA Standard 72 The FACP software also provides filters to remove tr...

Страница 5: ...pt to use this feature since it is not yet functional in this product Information on the availability of this feature will be made known on the manufacturer s internet site along with details on how to upgrade existing software 2 Printer Supervision Refer to the 9600 manual page 92 for information on this option Printer supervision when enabled will typically detect the removal of the printer cabl...

Отзывы: