2. Installation
Wiring the Control Switch
24
LDM-32F PN 50055:C 03/20/01
Wiring the Control Switch
Each LDM must be set for Alarm/Trouble mode by positioning slide switch
SW4 to the right, for the optional control switches to function (the
acknowledge/lamp test switch will work in either mode). In this configuration,
each LDM-32F and LDM-E32F provides 16 alarm drivers, 16 trouble drivers
and 16 control switches. The alarm and trouble drivers are assigned to host
FACP zones/points via user setup. Not all switches must be used - switches can
be wired only for desired functions.
• Switches must be UL listed to switch 5 volts DC @ 0.5mA.
• Switches must be key-lock type, secured in a locked enclosure or a
security key switch must be installed to control access.
• All switches must be installed in the same room as, and no more than
20 feet from, the LDM enclosure. Wiring must be in conduit.
• Optional zone/point control switches must be momentary type.
• Use the cables supplied in the cable kit to wire the control switches.
• See Appendices for specific FACP information.
Figure 16 Optional Zone/Point Control Switch Wiring
12
3
4
5
6
78
J5
J4
J1
SW1
SW2
SW3
SW4
SWITCH
MATRIX
L
d
m
s
wtwr
.cd
r
Switch #16
Switch #15
Switch #14
Switch #13
Switch #12
Switch #11
Switch #10
Switch #9
Switch #8
Switch #7
Switch #6
Switch #5
Switch #4
Switch #3
Switch #2
Switch #1
Lamp Test/Acknowledge
Switch (momentary)
Manual Evacuate
System Reset
Signal Silence
Acknowledge
Note:
Switches 5 - 16 are not used in this example.
Содержание LDM-32F
Страница 1: ...Lamp Driver Module LDM 32F Instruction Manual Document 50055 03 20 2001 Rev C PN 50055 C0 ECN 01 155...
Страница 4: ...4 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...
Страница 8: ...8 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...
Страница 16: ...1 Introduction Related Documentation 16 LDM 32F PN 50055 C 03 20 01 NOTES...
Страница 28: ...3 Operation Graphic Annunciator Lamps LEDs 28 LDM 32F PN 50055 C 03 20 01 NOTES...
Страница 30: ...4 LDM Communications Receive Transmit LDM 32F 30 LDM 32F PN 50055 C 03 20 01 NOTES...
Страница 50: ...Appendix B MS 9200 Configuration 50 LDM 32F PN 50055 C 03 20 01 NOTES...
Страница 61: ...LDM 32F PN 50055 C 03 20 01 61...
Страница 62: ...62 LDM 32F PN 50055 C 03 20 01...