B350LP PLUG-IN DETECTOR BASE

INSTALLATION INSTRUCTIONS

Before installing detectors, please thoroughly read the system wiring and installation manuals, and manual I56-407,
Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement,
zoning, and special applications. Copies of these manuals are available from Fire•Lite.

GENERAL DESCRIPTION

The B350LP Plug-in Detector Base is used with Fire•Lite models CP350 ionization, SD350 and SD350T photoelectronic de-
tectors, and H350 and H350R heat detectors

The B350LP base is intended for use in a 2-wire addressable system, with screw terminals provided for power (+ and –),
and remote annunciator connections. Communication takes place over the power (+ and –) lines.

BASE TERMINALS

NO.

FUNCTION

1

Power (–), Remote Annunciator (–)

2

Power (+)

3

Remote Annunciator (+)

A78-1318-00

F400-21-00

1

I56-954-01R

Fire•Lite Alarms, Inc., One Fire•Lite Place, Northford, CT 06472, 203-484-7161

Figure 1. Terminal Layout

SPECIFICATIONS

Diameter:

6.1 inches (155 mm)

Mounting:

4 inch (102 mm) square box with or without plaster ring
Min. Depth: 1.5 inches (38 mm)
4 inch Octagon Box, Min. Depth – 1.5 inches (38 mm)
3-1/2 inch Octagon Box, Min. Depth – 1.5 inches (38 mm)
Single Gang Box, Min. Depth –  1.5 inches (38 mm)

3

2

1

BASE
TERMINALS

TAMPER PROOF

TAB

Содержание B350LP

Страница 1: ... detectors The B350LP base is intended for use in a 2 wire addressable system with screw terminals provided for power and and remote annunciator connections Communication takes place over the power and lines BASE TERMINALS NO FUNCTION 1 Power Remote Annunciator 2 Power 3 Remote Annunciator A78 1318 00 F400 21 00 1 I56 954 01R Fire Lite Alarms Inc One Fire Lite Place Northford CT 06472 203 484 7161...

Страница 2: ...o smaller than AWG 18 However the screws and clamping plate in the base can accommodate wire sizes up to AWG 12 The use of twisted pair wiring or shielded cable for the power and loop is recom mended to minimize the effects of electrical interfer ence If shielded cable is used the shield connection to and from the detector must be continuous by using wire nuts crimping or soldering as appropriate ...

Страница 3: ...per resistant use needle nose pliers to break the smaller tab at the scribed line on the tamper resistant tab Figures 1 and 4A show the location of this tab on the detector mounting bracket To remove the detector from the base after it has been made tamper resistant remove the decorative ring by rotating it in either direction and pulling it away from the base Then insert a small screwdriver into ...

Страница 4: ... is not acceptable for three stripped wires to be under the same wiring terminal unless they are separated by a washer or a lug like the spade lug supplied with the model RA400Z See Figure 5 for installation A78 1473 00 Figure 5 Connection to Remote Annunciator Terminal STRIPPED WIRE WIRE WITH SPADE LUG F400 21 00 4 I56 954 01R 2000 Fire Lite Please refer to insert for the Limitations of Fire Alar...

Отзывы: