Calculating the Battery Size
NFPA Standard-Specific Requirements
MS-5UD and MS-10UD Series Manual —
P/N 52626:B1 6/30/2009
147
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP30 on the MS-5UD/MS-10UD main circuit board to supervise placement of
the 4XTMF module.
2. Refer to "4XTMF Transmitter Module Installation" on page 36 for detailed information.
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver
Model RS82.
+ -
Polarity Shown is
Normal Standby
4XTMF Transmitter Module
Cutting TBL Jumper allows the
reverse polarity circuit to open
with a system trouble condition
if no alarm condition exists.
Power-limited
Figure B.3 Remote Station Connection Using 4XTMF Module
+
-
(Dummy load with a 4.7K
Ω
, ¼ watt
resistor when no connection is made
)
Содержание MS-10UD Series