ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
79
Master Programming Level
Programming
To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that Relay 2 is fixed as a Trouble relay.
Selecting Relay 2 will have no effect on its programming. The following screen will appear for each relay to be programmed:
Pressing
1
for Type while viewing the Relay Screen will cause the following screens to be displayed:
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The
choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice.
Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Canadian Option
Pressing
1
while viewing System Setup Screen #3 will configure the FACP to comply with Canadian
requirements. The display will change to
Canadian Opt. On
. Each press of the
1
key will cause the display
to toggle between
Canadian Opt. On
and
Canadian Opt. Off
.:
Important!
For Canadian Applications, this option must be set to ON prior to any other panel programming.
The Canadian Options configures the FACP with the following as required by Canada:
•
The following monitor module type codes are
not
available:
monitor
non-latching supervisory
non-latching drill
non-latching process monitor
process monitor
hazard
tornado
medical alert
•
The auto-silence timer is fixed at 20 minutes and cannot be changed.
•
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian specifications.
•
The Positive Alarm Sequence and Pre-Signal option are not available for Canadian applications.
•
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
•
The F2 function key is automatically configured to perform a two-stage bypass when pressed.
•
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
•
AlarmNet supervision settings for Cellular and Ethernet communications are fixed at 3 minutes and cannot be changed regardless
of programming selection.
Waterflow Silenceable
Pressing
2
while viewing System Setup Screen #3 will allow the programmer to configure the system for
silenceable on nonsilenceable waterflow circuits. Each press of the
2
key will toggle the display between
Waterflow Sil. No
and
Waterflow Sil. Yes
. When
Waterflow Sil. No
is selected, all output devices associated
with a waterflow type input device, will be nonsilenceable. When
Waterflow Sil. Yes
is selected, all output
devices associated with a waterflow type input device, will be silenceable.
RELAY #
1=TYPE
ALARM
Relay Type Screen
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS_MON
Relay Screen #2
RELAY
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen #3
RELAY
1=MEDICAL
2=SILENCEABLE ALARM
3=CARBON MONOXIDE
Relay Screen #4
NOTE:
1.
AR (AutoResettable)
in
SUPERVISORY AR
and
PROCMON AR
means that a relay with the Supervisory and/or Process Monitor type
code, when activated, will automatically reset when the corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and deactivate when the FACP Alarm Silenced LED is
illuminated.
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE NO
System Setup Screen #3
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE NO
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE NO
System Setup Screen #3
Содержание ES-200X
Страница 137: ...ES 200X Series Manual P N LS10131 000FL E C 7 25 2018 137 Notes ...
Страница 164: ...164 ES 200X Series Manual P N LS10131 000FL E C 7 25 2018 ...
Страница 166: ...Cut along dotted line ...
Страница 168: ...One Fire Lite Place Northford CT 06472 1601 USA USA Phone 203 484 7161 Canada Phone 905 856 8733 www firelite com ...