26-0338 Issue 10 

 
 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Twinflex - V3 

Fire Detection & Alarm System 

 
 
 
 
 
 
 
 
 

Control Panel Engineering and 

Commissioning Manual 

 (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 

 
 
 
 
 
 
 
 
 
 
 

 
 
 

Содержание Twinflex V3

Страница 1: ...26 0338 Issue 10 Twinflex V3 FireDetection AlarmSystem Control Panel Engineering and Commissioning Manual TO BE RETAINED BY THE COMMISSIONING ENGINEER...

Страница 2: ...lexity and inherent importance of a life risk type system training on this equipment is essential and commissioning should only be carried out by competent persons Fike cannot guarantee the operation...

Страница 3: ...sting 19 General Operation 20 Introduction 20 Access Levels 20 Access Level 2 User Operating Diagram 2 4 Zone Panels 21 Access Level 2 User Operating Diagram 8 Zone Panels 22 LED Indication 23 Access...

Страница 4: ...necting Two Panels Together 42 Connecting More than Two Twinflex Panels Together 43 Magnetic Door Hold Units 44 Technical Data 45 Control Panel Specification 45 Resistor Colour Codes 46 Battery Calcul...

Страница 5: ...or organisation Anti Static Handling Guidelines Immediately prior to handling any PCBs or other static sensitive devices it is essential to ensure that a personal connection to earth is made with an...

Страница 6: ...a monitored conventional 24V relay circuit a volt free common fire relay and a volt free common fault relay There is also a multifunction non latching input programmable with options such as Class Ch...

Страница 7: ...l may be affected by extreme environmental conditions The position selected for its installation should therefore be clean and dry not subjected to high levels of vibration or shock and at least 2 met...

Страница 8: ...nels 72 hours 30 minutes in alarm 2 x 12v 2 1 Ah All 8 zone panels 24 hours 30 minutes in alarm 2 x 12v 3 2 or 3 3 Ah All 8 zone panels 72 hours 30 minutes in alarm 2 x 12v 7 2 Ah Note that the chargi...

Страница 9: ...uff Firecell Lifeline or equivalent Each zone requires a separate 2 core radial circuit from the control panel to the furthest point of the zone to a maximum of 500 metres In order to protect against...

Страница 10: ...Twinflex V3 Control Panel Engineering and Commissioning Manual 10 System Wiring Schematic The following schematic may prove useful as an aid to understanding the cable requirements for the system...

Страница 11: ...Ah sealed lead acid batteries connected in series in order to provide secondary backup power when the primary power fails This input is protected by the 3A fuse connected inline with the positive batt...

Страница 12: ...no indication and neither the Fire Relay nor the Remote Alarm Output will operate Mode 2 Remote Alarm excluding Remote Alarm Output On application of a 0V trigger the sounders will operate the control...

Страница 13: ...le changeover contacts rated at 30V DC 1A This contact will change state when the control panel enters the fault state and remain so until the fault condition is cleared All inductive loads should be...

Страница 14: ...Twinflex V3 Control Panel Engineering and Commissioning Manual 14 8 Zone Panels POWER SUPPLY 24V DC SWITCH MODE PSU LOCATED IN CONTROL PANEL BACK BOX POWER SUPPLY DC E RED BLACK...

Страница 15: ...state when the control panel enters the fire state and remain so until the system is reset All inductive loads should be diode protected eg using a 1N4004 diode to prevent back EMF However if this is...

Страница 16: ...imary power supply for the system Note Previously the control panel used a 24V AC input connected to a transformer mounted within the back box Ensure that the correct type of power supply is utilised...

Страница 17: ...CB Note that earlier versions of the 8 zone control panel had two sets of battery connections and required a 12V battery on each With the current versions a link wire is provided to allow the batterie...

Страница 18: ...orrect termination of the appropriate cables The repeater panel requires a multi core cable from the main control panel and must consist of the following Number of Cores Function Example 8 zone repeat...

Страница 19: ...g the key switch to the on position enables the controls buttons for Silence Alarms Reset System and Sound Alarms If these controls are not required then do not connect the terminals labelled EVAC SIL...

Страница 20: ...indicators are largely the same for the 2 4 and the 8 zone panels but there are a few differences Eg the 8 zone panel uses a key switch for Access Level 2 User entry whereas the 2 4 zone panels use a...

Страница 21: ...that the buzzer has been silenced It will switch off if the buzzer restarts and when the panel is operating normally ALARMS SILENCED This LED is illuminated when the alarm sounders are silenced and go...

Страница 22: ...when the panel is operating normally ALARMS SILENCED This LED is illuminated when the alarm sounders are silenced and goes off when the system is reset DISABLE ALARMS If button 3 is pressed at Access...

Страница 23: ...tion or more than one device is set to End of Line eg Optical Chamber removed Optical Chamber contaminated or dusty Output Module fault loop open circuit Output Module has no 24V DC supply 8 FAULT DIS...

Страница 24: ...PCB AC terminals 18 POWER LED Green Continuous This indicates that power is being supplied to the control panel from either the 230V AC mains supply or the standby batteries 19 BUZZER SILENCED LED Am...

Страница 25: ...ll light up continuously Access Level 2 User In the User state the panel is still active in detecting fire and fault conditions and will sound the alarm sounders when it is triggered The User Controls...

Страница 26: ...h on Silence Buzzer all panels 1 Press SILENCE BUZZER button 4 The fault buzzer will be silenced and the Buzzer Silenced LED will light The Buzzer Silenced LED will extinguish when the faults are clea...

Страница 27: ...n marked ACCESS A continuous buzzer tone will start 2 Press the button marked DISABLE ALARMS and then release them both The continuous buzzer tone will change to an intermittent tone if the alarms hav...

Страница 28: ...e above sequence again Access Level 3 Engineer In the Engineer state the panel is still active in detecting fire and fault conditions and will sound the alarm sounders when it is triggered The User Co...

Страница 29: ...require then press nothing until the system times out 15 seconds The continuous buzzer tone will stop and the lights mentioned above will turn off Your new setting is now active The continuous buzzer...

Страница 30: ...g until the system times out The continuous buzzer tone will stop and the lights mentioned above will turn off Your new setting is now active The continuous buzzer tone will stop and the lights mentio...

Страница 31: ...ill come on or go off accordingly Lamp Test Lamp Test and hold for 5 seconds All the lights will come on until the Lamp Test button is released Access Level 3 Engineer The functions override those des...

Страница 32: ...at they may be configured for Dwelling delayed or Communal instant I e The stairwell and communal corridors in a block of apartments will need to be wired on separate zones to the apartments If there...

Страница 33: ...to give an alarm confirmation warning at just that detector sounder Local Alarm Confirmation or across that entire zone Zonal Alarm Confirmation This continues until the situation is confirmed or res...

Страница 34: ...et up at Access Level 3 Engineer In the Engineer state the panel is still active in detecting fire and fault conditions and will sound the alarm To Configure the Zone Mode The ZONE MODE function allow...

Страница 35: ...ioned above will turn off The original setting is still active To Configure the Operation of the Repeater Outputs The repeater outputs may be configured as follows Mode Type Description 1 Fire Repeat...

Страница 36: ...l but it helps to build up the system in sections when commissioning a system for the first time 2 Apply the 230V AC mains supply before connecting the batteries 3 The control panel takes approximatel...

Страница 37: ...e essential that commissioning includes training for the users of the system and responsible persons User instructions and a Zone Chart should be left adjacent to the control panel As access to the sy...

Страница 38: ...witched off 9 Earth fault Ensure that all system earths are intact and not shorting to any other cables Permanent Zone Faults 1 More than one EOL switched on panel LED flashing faster than buzzer Remo...

Страница 39: ...ector General Faults 1 Sounder fault led this only activates for a fault on the conventional sounder circuit so check for O C S C and 4k7 EOL resistor 2 Remote Fire Output fault led this only activate...

Страница 40: ...tor is in fault check for dust contamination and that the optical chamber is locked on correctly 0 3 second flash or continuous The detector has triggered into the fire state and is not yet reset Chec...

Страница 41: ...igned for Fire Alarm Systems If the relay is a general purpose plug in relay then the diodes may need to be added externally Remote indication LEDs If a remote indication LED is required to indicate t...

Страница 42: ...WINFLEX V3 PANEL SELECTING MODE 2 ALARM INPUT OPERATION IF THE ALARM ORIGIONATED AT THE 3RD PARTY PANEL THEN RESETTING THIS WILL ALSO RESET THE TWINFLEX PANEL IF THE 3RD PARTY PANEL HAS A CLASS CHANGE...

Страница 43: ...panels may be reset individually if required Ensure that the Remote Alarm Input is programmed for Mode 4 operation The configuration shown above will cause the entire system to reset when the panel in...

Страница 44: ...ion in the event of an interruption to the power supply For assistance in choosing a suitable power supply unit standby batteries and Magnetic Door Hold units please contact your supplier If this is n...

Страница 45: ...ttery Capacity 72hr standby 2 x 12V 2 1 Ah 2 x 12V 7 2Ah Zone Output max 250 mA 250 mA Zone Voltage nominal 30V DC 27V DC Sounder Output Load max fused 500 mA 1A Sounder Output EOL 4k7 Remote Fire Out...

Страница 46: ...m the left and side of the resistor Blue 6 1 000 000 Violet 7 Grey 8 White 9 Gold 0 1 Silver 0 001 Technical Support For further technical support please contact your distributor Do not call the Fike...

Страница 47: ...5 12 619 MCP with sounder High 0 185 14 500 Flashpoint Beacon Only 0 223 5 520 Flashpoint Low 0 223 15 002 Flashpoint High 0 223 23 515 Soundpoint Low 0 185 12 619 Soundpoint High 0 185 14 500 Hipoint...

Страница 48: ...Installation Engineer Checked Commissioning Engineer Checked Zone cables installed correctly clipped or in containment All device bases and back boxes installed and terminated Cable insulation and con...

Страница 49: ...cted to the relevant zone The zone fault should clear Repeat for all zones Remainder of devices added one at a time with DIL switches set device installed and then allowed approx 30 50 secs to clear f...

Страница 50: ...Z6 Z7 Z8 Zone ve to ve with a temporary link at the last device Sounder circuit ve to ve with a temporary link at the last device Others A reading of approximately 1 ohm per 100 metres of 1 5 mm2 cab...

Страница 51: ...defined by the emergency plan for the premises To silence the alarm press SILENCE ALARMS then establish the cause of the alarm and enter the details in the log book Reset any Manual Call Points which...

Страница 52: ...that you may have accidentally set off the fire alarms then check the following If the fire alarm within your area only is sounding then check your own area for the cause of the alarm If this proves t...

Страница 53: ...Twinflex V3 Control Panel Engineering and Commissioning Manual 53 Engineers Notes...

Страница 54: ...Twinflex V3 Control Panel Engineering and Commissioning Manual 54 Engineers Notes...

Страница 55: ...Twinflex V3 Control Panel Engineering and Commissioning Manual 55 Engineers Notes...

Страница 56: ...an EOL signal simply switch this on page 13 14 Do not use an EOL resistor on unused zones switch the zone off page 29 How to go about the commissioning page 36 3 simple steps to fault finding page 38...