INSTALLATION AND MAINTENANCE INSTRUCTIONS 

 

302-0004 Twinflex Hipoint  
 

 

 

26-0378 Issue 5

 

 

 
 
Introduction  

 
The Twinflex Hipoint unit allows for audible indication when the system enters an 
alarm condition. This device is compatible with the Twinflex 2-wire range of Fire 
Alarm equipment and comprises a 2-wire zone-powered sounder. This device may 
be installed on the same zone as the Multipoint detector/sounder and associated 
Twinflex devices

.

 

 
Before Installation 

 

The Sounder must be installed in compliance with the control panel installation manual. The installation must also 
meet the requirements of any local authority. For maximum performance the detector should be installed in 
compliance with BS5839 Pt1 : 2002 + A2 : 2008. 

 

Spacing 

 

Fike recommends spacing of sounders in accordance with BS5839 Pt1. For more specific information regarding 
sounder spacing, placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008. 
 

Device Installation 

 

Fix the back box in a suitable position using at least two screw holes/slots, remembering to allow enough cable 
length for installation. All wiring must be installed in compliance with the recommendations laid out by BS5839 Pt1 : 
2002 as well as any special recommendations documented in the control panel installation manual.

 

 

Connections 

 

The cabling should be 2-core 1.5mm

2

 screened/earthed and fire resistant, of an MICC 

or FP200 equivalent type and is to be in the form of a 2-core radial circuit terminating 
at the End of Line device.  
 
No screen connection is allowed for within the device. Incoming and outgoing cable 
screens must therefore be connected through using a suitable connector. It is 
important to maintain the screen continuity in order to protect against data corruption 
from interference. 
 
Once all testing has been carried out on the cabling and 

continuity & insulation

 has 

been proven, the Hipoint front may be fitted. The Hipoint front is fitted by locating the 
rubber seal in the groove on the back box and then pushing the front unit gently 
home. The four fixing screws may then be tightened as required. 

 
Remember that the device at the end of the line must have its EOL signal activated using the 
relevant DIL switch.  Do not use a resistor or capacitor (or another manufacturer’s End of Line 
device) as the end of line, as this may prevent correct operation of the zone. 

 

 
 

 

 
 
 
 
 
 
 
 

EARTH 

ZONE -VE 

ZONE +VE 

SCREEN 

SCREEN 

SCREEN 

SCREEN 

TWINFLEX HIPOINT 

TWINFLEX HIPOINT 

CONTROL PANEL 

TO ACTIVATE EOL

MOVE SWITCH 1 TO

“ON” POSITION

–VE

–VE

+

VE

+

VE

+

+

4 3 2 1

ON