General Description

The Twinflex Soundpoint unit allows for audible indication when the system enters an alarm 

condition. This device is compatible with the Twinflex 2-wire range of Fire Alarm equipment 

and comprises a 2-wire zone-powered sounder. This device may be installed on the same 

zone as the Multipoint detector/sounder and associated Twinflex devices.

Before Installation

The MCP must be installed in compliance with the control panel installation manual. 

The installation must also meet the requirements of any local authority.

Spacing

Fike recommends spacing of call points in accordance with any local authority. 

Device Installation

Surface Mounting

Fix the surface back box to a flat vertical surface using at least two of the four mounting 

holes provided.  The back box may be drilled to allow cable access as required. A 

20mm  hole  is  already  provided  at  the  rear.  Zone  cabling  may  be  connected  to  the 

terminals in the back box.

Flush Mounting

The Soundpoint may be flush mounted utilising the optional adaptor plate, combined 

with any standard single gang flush mounting back box (with a minimum internal depth 

of 47mm). 

After installing the back box securely, attach the adaptor plate using the two screws 

provided, and terminate your cables directly into a flying terminal block. 

Installation 2nd Fix

Once all testing has been carried out on the cabling and ‘continuity & integrity’ has 

been proven, the Soundpoint front may be installed. 

Connect  the  wires  from  the  Soundpoint  front  in  to  the  appropriate  terminals  in  the 

back box according to the wire colours. The Soundpoint front may then be installed by 

locating the upper mounting hooks into the back box and then pushing the unit gently 

home. The single fixing screw may then be tightened as required.  

Please remember that all high voltage testing must be carried out before the installation 

of the Soundpoint front unit, otherwise the electronics will be damaged.