INSTALLATION AND MAINTENANCE
INSTRUCTIONS
http://www.fike.co.uk/
resource-downloads/twinflex/
General Description
The Twinflex Soundpoint unit allows for audible indication when the system enters an alarm
condition. This device is compatible with the Twinflex 2-wire range of Fire Alarm equipment
and comprises a 2-wire zone-powered sounder. This device may be installed on the same
zone as the Multipoint detector/sounder and associated Twinflex devices.
Before Installation
The MCP must be installed in compliance with the control panel installation manual.
The installation must also meet the requirements of any local authority.
Spacing
Fike recommends spacing of call points in accordance with any local authority.
Device Installation
Surface Mounting
Fix the surface back box to a flat vertical surface using at least two of the four mounting
holes provided. The back box may be drilled to allow cable access as required. A
20mm hole is already provided at the rear. Zone cabling may be connected to the
terminals in the back box.
Flush Mounting
The Soundpoint may be flush mounted utilising the optional adaptor plate, combined
with any standard single gang flush mounting back box (with a minimum internal depth
of 47mm).
After installing the back box securely, attach the adaptor plate using the two screws
provided, and terminate your cables directly into a flying terminal block.
Installation 2nd Fix
Once all testing has been carried out on the cabling and ‘continuity & integrity’ has
been proven, the Soundpoint front may be installed.
Connect the wires from the Soundpoint front in to the appropriate terminals in the
back box according to the wire colours. The Soundpoint front may then be installed by
locating the upper mounting hooks into the back box and then pushing the unit gently
home. The single fixing screw may then be tightened as required.
Please remember that all high voltage testing must be carried out before the installation
of the Soundpoint front unit, otherwise the electronics will be damaged.
313-0021(RED) 313-0022(WHITE) TWINFLEX SOUNDPOINT