INSTALLATION AND MAINTENANCE INSTRUCTIONS 

 
302-0023 Twinflex 
Flashpoint Weatherproof 

 

 

26-0693 Issue 3 

General Description 

 

The Twinflex Weatherproof Flashpoint device provides visual indication when 
the system enters an alarm condition. This device is compatible with the 
Twinflex 2-wire range of Fire Alarm equipment and comprises a 2-wire zone-
powered visual indication beacon. This device may be installed on the same 
zone as the Multipoint detector/sounder and associated Twinflex devices

 
Before Installation 

 

The Flashpoint must be installed in compliance with the control panel 
installation manual. The installation must also meet the requirements of any 
local authority. For maximum performance the Flashpoint should be installed 
in compliance with BS5839 Pt1 : 2002 + A2 : 2008. 

 

Spacing 
 

Fike recommends spacing of sounders and strobes in accordance with BS5839 Pt1. For more specific information 
regarding spacing, placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008. 

 

Device Installation 
 

Pre-drill a minimum of 2 fixing holes in the back box as required. Fix the back box in a suitable position, 
remembering to allow enough space for the correct termination of the appropriate fire resistant cable. All wiring 
must be installed in compliance with the recommendations laid out by BS5839 Pt1 : 2002 as well as any special 
recommendations documented in the control panel installation manual.  

 
Connections 

 

The cabling used should be 

2-core 1.5mm

2

 

screened/earthed and fire resistant, of an 
MICC or FP200 equivalent type and is to be in 
the form of a 2-core radial circuit terminating at 
the End of Line device. Cables may be 
terminated into the connectors mounted in the 
back box, as shown below. Also please ensure 
that you use suitable cable glands for cable 
entry in order to maintain the IP rating.  
 
Care should be taken when terminating devices to ensure all cables are correctly sleeved and connections are 
secure. Improper connections will prevent a system from responding properly in the event of a fire. Please 
remember that all high voltage testing must be carried out before the installation of the Flashpoint front unit as this 
may cause damage. It is important to maintain the screen continuity in order to protect against data corruption from 
interference. 

 

CONTROL PANEL

ZO

NE +VE

ZON

E

 -VE

SCRN

ZONE +V

E

(RED)

ZONE

 -

V

E

(BLU

E)

SCR

E

EN 

(S

CRN)

TWINFLEX 

FLASHPOINT

ZO

N

E

 +

V

E

 

(R
E

D

)

ZO

NE -

V

E

(B
L

U

E)

SCRE

EN 

(S

CR

N)

TWINFLEX 

FLASHPOINT

RED

SCRN

BLUE

Отзывы: