background image

 

26-0981 Issue 2 

 

 

 

 
 

 

General Description 

 

The Sita Multipoint ASD detector base allows for the connection of Multipoint devices to the Sita loop. This base is 
only compatible with the addressable Multipoint ASD detector for the Sita200plus, Duonet and Quadnet ranges of 
control panels. 

 
Before Installation 

 

The detector must be installed in compliance with the control panel installation manual. The installation must also 
meet  the  requirements  of  any  local  authority.  For  maximum  performance  the  detector  should  be  installed  in 
compliance to BS5839 Pt1 : 2002 + A2 : 2008. 

 

Spacing 
 

Fike  recommends  spacing  detectors  in  accordance  with  BS5839  Pt1.  Due  to  the  effects  of  IR  and  possible 
magnetic interference, detectors should not be fitted any closer than 500mm (preferably 1000mm) to a light fitting or 
any other source of IR. In addition to this recommendation, the device should be mounted so that the indication LED 
is facing towards the light source. For more specific information regarding detector spacing, placement and special 
applications please refer to BS5839 Pt1 : 2002 + A2 : 2008. 

 

Base Installation 
 

All wiring must be installed in compliance with the recommendations laid out by BS5839 Pt1 : 2002 as well as any 
special recommendations documented in the control panel installation manual. 

The cabling used should be of a 

2-core 1.5mm

2

 screened, fire resistant type with the following characteristics: 

 

 

Max Capacitance Core to Screen 

180pf / m 

 
 

Max Capacitance Core to Core  . 

100pf / m 

 
 

Max Inductance . 

1.0mH / Km 

 
 

Max Resistance Two Core Screened 1.5mm² 

12.1 

Ώ

 / Km 

 
It is to be wired in the form of a screened 2-core loop returning to the control panel. The use of spurs on 
this  system  is  not  permitted.

  Cables  may  be  terminated  into  the  connectors  mounted  in  the  base,  as  shown 

below. Care should be taken when terminating devices to ensure all cables are correctly sleeved and connections 
are secure. Improper connections will prevent a system from responding properly in the event of a fire. 
 
 
 

 

Terminal 

Description 

 

1  /  LOOP 0V 

Loop –ve In & Out 

(also Remote LED 0V) 

2  /  LOOP +IN 

Loop +ve In 

 

3  /  LOOP +OUT 

Loop +ve Out 

 

4  /  AUX +VE 

Auxve 

(also Remote LED +ve) 

5  /  AUX –VE 

Auxiliary -ve 

 

SCRN 

Cable Screen 

 

 

 
 
 

INSTALLATION AND MAINTENANCE INSTRUCTIONS 
 
 

905-0001 Sita Multipoint ASD 
Detector Base 

 


 


 


 


 


 


 


 


 


 

Отзывы: