26-1075 Issue 5 

 

 

 

 

General Description 

 

The Sita Manual Call Point allows for user activation of the fire alarm system.  

Once operated the device latches into the alarm position and requires  manually 

resetting via a special key. The MCP is an addressable unit that attaches to the loop. 

Digital communication technology to the control panel is implemented allowing for 

accurate data transfer at high transmission speeds. This device is only compatible 

with the Sita200plus, Duonet and Quadnet ranges of control panel. 

 

 

Before Installation 

 

The MCP must be installed in compliance with the control panel installation manual. 

The installation must also meet the requirements of any local authority. For maximum 

performance the call point should be installed in compliance with  

BS5839 Pt1 : 2002 + A2 : 2008. 

 

 

Spacing 

 

Fike recommends spacing of call points in accordance with BS5839 Pt1 2002. For more specific information 

regarding MCP spacing, placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008. 

 

 

Device Installation 

 

All wiring must be installed in compliance with the recommendations laid out by BS5839 Pt1 : 2002 as well as any 

special  recommendations documented in the control panel installation manual. All wiring must be installed in 

compliance with the recommendations laid out by BS 5839 as well as any special recommendations documented in 

the control panel installation manual. 

The cabling used should be of a 2-core 1.5mm

2

 screened, fire resistant 

type, with the following characteristics: 

 

 

Max Capacitance Core to Screen ................................................... 180pF / m 

Max Capacitance Core to Core....................................................... 100pF / m 

Max Inductance ............................................................................... 1.0mH / km 

Max Resistance Two Core Screened 1.5mm² ................................ 12.1Ω / km 

 

It is to be wired in the form of a screened 2-core loop returning to the control panel. The use of spurs on 

this system is not permitted.

 Cables may be terminated into the connectors, as shown overleaf. If the device is 

flush mounted then the loop cabling must be attached to the device via a suitable connection block (not supplied). 

Cut off crimp fork terminals, strip ends for desired length and twist conductor strands together neatly  as shown 

below. Terminate your cables directly into a flying terminal block. If using a metal back box, do not connect the 

screen to the back box earth terminal or allow it to come into contact with the metal box 

 

 

 

INSTALLATION AND MAINTENANCE INSTRUCTIONS 

 

 

403-0006 Sita Manual Call Point 