26-1075 Issue 5
General Description
The Sita Manual Call Point allows for user activation of the fire alarm system.
Once operated the device latches into the alarm position and requires manually
resetting via a special key. The MCP is an addressable unit that attaches to the loop.
Digital communication technology to the control panel is implemented allowing for
accurate data transfer at high transmission speeds. This device is only compatible
with the Sita200plus, Duonet and Quadnet ranges of control panel.
Before Installation
The MCP must be installed in compliance with the control panel installation manual.
The installation must also meet the requirements of any local authority. For maximum
performance the call point should be installed in compliance with
BS5839 Pt1 : 2002 + A2 : 2008.
Spacing
Fike recommends spacing of call points in accordance with BS5839 Pt1 2002. For more specific information
regarding MCP spacing, placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008.
Device Installation
All wiring must be installed in compliance with the recommendations laid out by BS5839 Pt1 : 2002 as well as any
special recommendations documented in the control panel installation manual. All wiring must be installed in
compliance with the recommendations laid out by BS 5839 as well as any special recommendations documented in
the control panel installation manual.
The cabling used should be of a 2-core 1.5mm
2
screened, fire resistant
type, with the following characteristics:
Max Capacitance Core to Screen ................................................... 180pF / m
Max Capacitance Core to Core....................................................... 100pF / m
Max Inductance ............................................................................... 1.0mH / km
Max Resistance Two Core Screened 1.5mm² ................................ 12.1Ω / km
It is to be wired in the form of a screened 2-core loop returning to the control panel. The use of spurs on
this system is not permitted.
Cables may be terminated into the connectors, as shown overleaf. If the device is
flush mounted then the loop cabling must be attached to the device via a suitable connection block (not supplied).
Cut off crimp fork terminals, strip ends for desired length and twist conductor strands together neatly as shown
below. Terminate your cables directly into a flying terminal block. If using a metal back box, do not connect the
screen to the back box earth terminal or allow it to come into contact with the metal box
INSTALLATION AND MAINTENANCE INSTRUCTIONS
403-0006 Sita Manual Call Point